48
C200HX/C200HG/C200HE PCs
Section 6-2
•
Some of the other bits that appear in the program are allocated to the Mas-
ter Unit. Refer to the DeviceNet (CompoBus/D) Operation Manual (Cat. No.
W267)) for details.
Word
Bit
Contents
CIO 060
06000
Write Start Bit
06001
Read Start Bit
DM Area words
Contents
D0008 to D0009
First word of write command response storage area
D0010
Response monitoring time
D0011
Command byte length
D0012 to D0015
DeviceNet explicit message FINS header code
D0016 to D0019
FINS command header code (write)
D0020 to D0027
Alarm 1 temperature write data for control points 0 to 7
D0036 to D0037
First word of read command response storage area
D0038
Response monitoring time
D0039
Command byte length
D0040 to D0043
DeviceNet explicit message FINS header code
D0044 to D0047
FINS command header code (read)
D0080 to D0082
Response block end code comparative data
D0054 to D0059
Response block header code storage area
D0060 to D0067
Alarm 1 temperature read data for control points 0 to 7