Output Variable Change Rate Limit Value Read: RG
Section 4-16
4-16 Output Variable Change Rate Limit Value Read: RG
Function
This command is used to read the output variable change rate limit values that
have been set at a control point.
Command
Response
1.
The response block for Output Variable Change Rate Limit Value Read
(RG) does not include read data if the end code of the response block is
other than 00.
2.
Refer to
2-4 End Codes
.
Communications Example
In this example, the E5ZE is operated with Output Variable Change Rate Limit
Value Read (RG) under the following conditions.
Unit no.:
1
Memory Bank no.: 2
Control Point:
3
Output Variable Change Rate Limit Value: 60.0% per sampling period
Command
Response
4-17 Memory Write: WE
Function
This command is used to write the setting data set with the E5ZE to the mem-
ory.
When the E5ZE is turned ON, the setting data stored in the memory will be
read by the E5ZE automatically for temperature control use.
@ R G 0 0
s
Control
point
Terminator
*
FCS
x16
x16
Unit
Bank
Header code
Data code
1
0
@ R G
s
Decimal point
Terminator
*
Output variable change
rate limit value
FCS
x16
x16
Unit
Read data
Header code
End code
x16
x16
x10
x10
x10
x10
1
1
1
0
0
0
2
-1
@ 0 1 R G 2 3 0 0 5 5
s
*
@ 0 1 R G 0 0 0 6 0 0 5 2
s
Normal end
60.0%/(Sampling period)
*