63
Multi-vendor Applications
Appendix A
Item
ID Contents
Get
(read)
Set
(write)
Value
Object interface 1
Attributes
1
State
Yes
No
---
2
Instance type
Yes
No
00 (hexadecimal)
3
Transport class trigger
Yes
No
83 (hexadecimal)
4
Produced connection ID
Yes
No
---
5
Consumed connection ID
Yes
No
---
6
Initial comm. characteristics
Yes
No
21 (hexadecimal)
7
Produced connection size
Yes
No
FFFF (hexadecimal)
8
Consumed connection size
Yes
No
FFFF (hexadecimal)
9
Expected packet rate
Yes
Yes
---
12
Watchdog time
-
out action
Yes
No
01 or 03
13
Produced connection path length
Yes
No
00
14
Produced connection path
Yes
No
---
15
Consumed connection path length
Yes
No
00
16
Consumed connection path
Yes
No
---
17
Production inhibit time
Yes
No
---
Item
DeviceNet service
Parameter option
Object interface 1
Services
05
Reset
No
0E
Get_Attribute_Single
No
10
Set_Attribute_Single
No
Item
Section
Information
Max. number of interfaces
Object interface 2
Interface type
Polled I/O
1
Production trigger
Cyclic
---
Transport type
Server
---
Transport class
2
---
Item
ID Contents
Get
(read)
Set
(write)
Value
Object interface 2
Attributes
1
State
Yes
No
---
2
Instance type
Yes
No
01 (hexadecimal)
3
Transport class trigger
Yes
No
82 (hexadecimal)
4
Produced connection ID
Yes
No
---
5
Consumed connection ID
Yes
No
---
6
Initial comm. characteristics
Yes
No
01 (hexadecimal)
7
Produced connection size
Yes
No
1C00 (hexadecimal)
8
Consumed connection size
Yes
No
1200 (hexadecimal)
9
Expected packet rate
Yes
Yes
---
12
Watchdog time
–
out action
Yes
No
00
13
Produced connection path length
Yes
No
00
14
Produced connection path
Yes
No
---
15
Consumed connection path length
Yes
No
00
16
Consumed connection path
Yes
No
---
17
Production inhibit time
Yes
No
---
Item
DeviceNet service
Parameter option
Object interface 2
Services
05
Reset
No
0E
Get_Attribute_Single
No
10
Set_Attribute_Single
No