Set Point Write: WS
Section 3-1
3-1
Set Point Write: WS
Function
This command is used to write the set point required for temperature control
to a control point.
1.
Setting Unit Write (Wt) must be used to set the temperature setting unit of
a control point to 1 or 0.1.
2.
Set Point Write (WS) cannot be used at the designated control point being
auto
-
tuned.
3.
The possible setting data range will be -1,999 to 9,999 if the E5ZD
-
SDL
Setting Display Unit is used with the E5ZE after pin number 4 of the FUNC-
TION switch is set to ON and the temperature setting unit is set to 0.1.
Setting Data Range
Command
When Setting Unit is 1
When Setting Unit is 0.1
Setting unit
1
0.1
°
C or
°
F
°
C
°
F
°
C
°
F
Default
0000
00000
Setting Data
K
-200 to 1300
-300 to 2300
-2000 to 13000
-3000 to 23000
J
-100 to 0850
-100 to 1500
-1000 to 08500
-1000 to 15000
R
0000 to 1700
0000 to 3000
00000 to 17000
00000 to 30000
S
0000 to 1700
0000 to 3000
00000 to 17000
00000 to 30000
T
-200 to 0400
-300 to 0700
-2000 to 04000
-3000 to 07000
E
0000 to 0600
0000 to 1100
00000 to 06000
00000 to 11000
B
0100 to 1800
0300 to 3000
01000 to 18000
03000 to 30000
N
0000 to 1300
0000 to 2300
00000 to 13000
00000 to 23000
L
-100 to 0850
-100 to 1500
-1000 to 08500
-1000 to 15000
U
-200 to 0400
-300 to 0700
-2000 to 04000
-3000 to 07000
W/Re5
-
26
0000 to 2300
0032 to 4100
00000 to 23000
00320 to 41000
PL
-
II
0000 to 1300
0000 to 2300
00000 to 13000
00000 to 23000
Pt100
-100 to 0500
-100 to 0900
-1000 to 05000
-1000 to 09000
JPt100
-100 to 0500
-100 to 0900
-1000 to 05000
-1000 to 09000
@ W S 0 0
Setting data
Data code
Terminator
FCS
x16
x16
Header code
Set point
x10
x10
x10
x10
Bank
Or minus sign (-)
Control
point
*
1
0
s
Unit
3
2
1
0
Decimal point
Setting data
Or minus sign (-)
Bank
Data code
Terminator
@
Unit
s
FCS
W
S
Header code
0
0
Set point
x16
x16
x10
x10
x10
x10
x10
Control
point
*
1
0
3
2
1
0
-1