82
End Codes
Section 2-4
2-4
End Codes
List of End Codes
End
code
Name
Command
Cause
Remedy
00
Normal End ---
---
---
01
Prohibited
Command
WB, WN, WV,
WI*, WS, WT,
WH, WK, WL,
WG, Wj, Wk,
Wl**, WD, WC,
OS, OM
The designated control point is being
auto
-
tuned.
Send the command after interrupting
the auto
-
tuning of the control point.
W#, MC
The E5ZE is in control operation or
manual operation at the designated
control point.
Send the command after interrupting
the control operation or manual opera-
tion at the control point.
WM
The memory bank designation method
has been set to contact input designa-
tion.
Set the memory bank designation
method to communications designation.
Refer to the E5ZE Operation Manual for
details.
The designated control point is being
auto
-
tuned.
Send the command after interrupting
the auto
-
tuning of the control point.
AS
The control operation at the designated
control point is stopped.
Execute the auto
-
tuning after the E5ZE
starts temperature control at the control
point.
The designated control point is already
being auto
-
tuned.
Correct the program because the con-
trol point being auto
-
tuned does not
accept Auto
-
tuning Start (AS).
WO
The E5ZE was not in manual operation
at the designated control point.
Send the command after sending Man-
ual Operation Start (OM) to the E5ZE to
start the manual operation.
WU
The E5ZE is in temperature control
operation or manual operation at the
designated control point.
Send the command after interrupting
the temperature control operation or
manual operation at the control point.
HB Alarm and HS Alarm Point Write
(WU) with data code 02 was sent to an
E5ZE model without HB or HS alarm
function.
This command cannot be sent to any
E5ZE model without HB or HS alarm
function.
WW, RW
These commands were sent to an
E5ZE model without HB or HS alarm
function.
These commands cannot be sent to
any E5ZE model without HB or HS
alarm function.
The HB or HS alarm function of the
designated control point was not valid.
Before sending these commands, send
HB Alarm and HS Alarm Point Write
(WU) to the designated control point so
that the HB and HS alarms of the desig-
nated control point will be valid.
RZ
The E54
-
E8CT CT Input Unit is not con-
nected to the E5ZE.
Connect the E54
-
E8CT CT Input Unit to
the E5ZE.
04
Invalid
Address
---
A nonexisting control point, memory
bank, or data code was designated.
Designate the control point, memory
bank, and data code correctly.
A was designated for the control point
and memory bank and AA was desig-
nated for the data code simultaneously.
A or AA can be used only once in each
command block.