96
Integral Time Read: RN
Section 3-8
3-8
Integral Time Read: RN
Function
This command is used to read the integral time that have been set at a control
point.
Command
Response
1.
The response block for Integral Time Read (RN) does not include read
data if the end code of the response block is other than 00.
2.
Refer to
2-4 End Codes
.
Communications Example
In this example, the E5ZE is operated with Integral Time Read (RN) under the
following conditions.
Unit no.:
1
Memory Bank no.: 2
Control Point:
3
Integral Time:
50 s
Command
Response
@ R N 0 0
Data code
Terminator
FCS
x16
x16
Header code
*
Unit
Bank
Control
point
s
1
0
@ R N
Read data
Terminator
FCS
x16
x16
Header code
Constant I
*
Unit
x10
x10
x10
x10
x16
x16
End code
s
1
1
1
0
0
0
3
2
*
@ 0 1 R N 2 3 0 0 5 C
s
*
@ 0 1 R N 0 0 0 0 5 0 5 8
s
50 s
Normal end