95
Integral Time Write: WN
Section 3-7
3-7
Integral Time Write: WN
Function
This command is used to write the integral time to a control point.
Integral Time Write (WN) cannot be used at a control point being auto
-
tuned.
Setting Data Range
If the constant I of a control point set to 0000 is used for temperature control
with the E5ZE, the E5ZE will not be in integral operation at the control point.
Command
Response
Communications Example
In this example, the E5ZE is operated with Integral Time Write (WN) under the
following conditions.
Unit no.:
1
Memory Bank no.: 2
Control Point:
3
Integral Time:
50 s
Command
Response
Setting unit
1
Setting time unit
s
Default
0000
Setting data
0000 to 3999
@ W N 0 0
Setting data
Data code
Terminator
FCS
x16
x16
Header code
Constant I
*
Unit
x10
x10
x10
x10
Bank
Control
point
s
1
1
0
0
2
3
@ W N
*
FCS
End code
Unit
x16
x16
x16
x16
Header code
Terminator
s
1
1
0
0
@ 0 1 W N 2 3 0 0 0 0 5 0 5 C
s
*
50 s
@ 0 1 W N 0 0 5 8
s
Normal end
*