21
DeviceNet Explicit Messages Set Values and Measurement
Section 4-4
4-3-3
Control Data for Sending DeviceNet Explicit Messages Using
CMND(194/490) or IOWR(223)
4-4
DeviceNet Explicit Messages Set Values and Measurement
Values
This section provides tables that can be used when setting and monitoring the
set values for all control points. The tables are given by variable type.
4-4-1
Commonly Used Set Values
Variable Type: 90
Master Unit
Unit No. 2
PC
Explicit message
IOWR(223) control data
Destination
node address
Destination Unit address FE or 12
(12 indicates Special I/O Unit No. 2)
Destination node address
CMND(194/490) control data
No. of command data bytes
No. of response data types
Send to local network
Destination Unit address FE or 12
(12 indicates Special I/O Unit No. 2)
Resend once
No.
Address
Set value or measurement value
Data setting or monitoring range
Data type
1
0000
Control point 0 process value
Range: Depends on sensor type used.
(See note 4.)
Unit:Depends on setting (either 0.1
°
C/
°
F or
1
°
C/
°
F)
Numeric
Read only
2
0001
Control point 1 process value
3
0002
Control point 2 process value
4
0003
Control point 3 process value
5
0004
Control point 4 process value
6
0005
Control point 5 process value
7
0006
Control point 6 process value
8
0007
Control point 7 process value
9
000C
Alarm 1 status
Range: 0000 to 80FF
Status
Read only
Bit contents same
as remote I/O
contents.
10
000D
Alarm 2 status
Range: 0000 to 80FF
11
000E
Auto
–
tuning status
Range: 0000 to 80FF
12
000F
HB alarm status
Range: 0000 to 80FF
13
0010
HS alarm status
Range: 0000 to 80FF