Section 4-7
4-7
Manual Reset Value Write: WK
Function
This command is used to write the percentages of manual reset value to a
control point when there are offset at the control point in P or PD control oper-
ation.
1.
The offset at the control point can be corrected by adjusting the manual re-
set value written to the control point.
2.
Manual Reset Value Write (WK) cannot be used at a control point being
auto
-
tuned.
Setting Data Range
Command
Response
Communications Example
In this example, the E5ZE is operated with Manual Reset Value Write (WK)
under the following conditions.
Unit no.:
1
Memory Bank no.:
2
Control Point:
3
Manual Reset Value: 70.0%
Command
Response
Setting unit
0.1
Manual reset value unit
%
Default
0500
Setting data
0000 to 1000
@ W K 0 0
s
Decimal point
Control
point
Data code
Terminator
*
Manual reset value
FCS
x16
x16
Unit
Bank
Setting data
Header code
x10
x10
x10
x10
1
1
0
0
2
-1
@ W K
s
*
FCS
End code
Unit
x16
x16
x16
x16
Header code
Terminator
1
1
0
0
@ 0 1 W K 2 3 0 0 0 7 0 0 5 B
s
*
70.0%
@ 0 1 W K 0 0 5 D
s
Normal end
*