101
Output Operation (Normal/Reverse) Write: WU
Section 3-13
3-13 Output Operation (Normal/Reverse) Write: WU
Function
This command is used to designate the normal or reverse operation of a con-
trol point.
1.
Output Operation Write (WU) enables the E5ZE in heating and cooling
control operation to change its heating
-
side control to cooling
-
side control
and vice versa at a control point simultaneously.
2.
Output Operation Write (WU) cannot be used at a control point in manual
operation, control operation or auto
-
tuning operation.
Setting Data Range
Command
Response
Communications Example
In this example, the E5ZE is operated with Output Operation Write (WU)
under the following conditions.
Unit no.: 1
Control Points 0, 2, 4, and 6: Direct operation
Control Points 1, 3, 5, and 7: Reverse operation
Default
0000 (All control points in reverse operation)
Setting code
00 to FF
@ W U 0 0 0 0 0 0
s
Always 00
Setting data
Data code
Terminator
FCS
x16
x16
Header code
Setting
code
*
Unit
x16
x16
x16
x16
7 6 5 4 3 2 1 0
Control point
Bit
Normal Reverse
Point 0
1
0
Point 1
1
0
Point 2
1
0
Point 3
1
0
Point 4
1
0
Point 5
1
0
Point 6
1
0
Point 7
1
0
Bit number
1
1
0
0
3
2
@ W U
s
*
FCS
End code
Unit
x16
x16
x16
x16
Header code
Terminator
1
1
0
0