22
DeviceNet Explicit Messages Set Values and Measurement
Section 4-4
14
0011
Temperature control status
(See note 7.)
Range: 0000 to 811F
Status
Read only
15
0012
Operation start/stop
(See notes 3 and 6.)
Range: 0000 to 00FF (Default: 0000)
Status
Read
16
0013
Control point 0 set point
Range: Depends on sensor type used.
(See notes 1 and 4.)
Unit:
Depends on setting (either 0.1
°
C/
°
F or 1
°
C/
°
F)
Numeric
Read
17
0014
Control point 1 set point
18
0015
Control point 2 set point
19
0016
Control point 3 set point
20
0017
Control point 4 set point
21
0018
Control point 5 set point
22
0019
Control point 6 set point
23
001A
Control point 7 set point
24
001F
Auto
-
tuning start/stop
(See note 2.)
Range: 0000 to 00FF
Default: 0000
Status
Write only
25
0020
Control point 0 alarm 1 temperature
Range: D8F1 to 7350 (-999.9 to 3000.0)
when setting unit is 0.1
°
C/
°
F. (See note 4.)
Range: D8F1 to 270F (-9999 to 9999)
when setting unit is 1
°
C/
°
F.
Default: 0000 (0.0 or 0)
Numeric
Read/write
26
0021
Control point 1 alarm 1 temperature
27
0022
Control point 2 alarm 1 temperature
28
0023
Control point 3 alarm 1 temperature
29
0024
Control point 4 alarm 1 temperature
30
0025
Control point 5 alarm 1 temperature
31
0026
Control point 6 alarm 1 temperature
32
0027
Control point 7 alarm 1 temperature
33
002C
Control point 0 alarm 2 temperature
Range: D8F1 to 7530 (-999.9 to 3000.0)
when setting unit is 0.1
°
C/
°
F. (See note 4.)
Range: D8F1 to 270F (-9999 to 9999)
when setting unit is 1
°
C/
°
F.
Default: 0000 (0.0 or 0)
Numeric
Read/write
34
002D
Control point 1 alarm 2 temperature
35
002E
Control point 2 alarm 2 temperature
36
002F
Control point 3 alarm 2 temperature
37
0030
Control point 4 alarm 2 temperature
38
0031
Control point 5 alarm 2 temperature
39
0032
Control point 6 alarm 2 temperature
40
0033
Control point 7 alarm 2 temperature
41
0038
Control point 0 input shift value
Range: FC19 to 03E7 (-99.9 to 99.9)
(See note 1.)
Unit:
0.1
°
C or
°
F
Default: 0000 (0.0)
Numeric
Read/write
42
0039
Control point 1 input shift value
43
003A
Control point 2 input shift value
44
003B
Control point 3 input shift value
45
003C
Control point 4 input shift value
46
003D
Control point 5 input shift value
47
003E
Control point 6 input shift value
48
003F
Control point 7 input shift value
No.
Address
Set value or measurement value
Data setting or monitoring range
Data type