35
End Codes
Section 5-1
DeviceNet Error Codes
5-1-3
Checking 0101 (Read) and 0102 (Write) Commands End Codes
Read
The responses to commands 0101 and 0102 are described below. The com-
mands have ended normally when the response code is 0000.
Write
Meaning
A processing error has occurred in the E5ZE.
Processing
Turn ON the power to E5ZE again. If the E5ZE is set to continuous communi-
cations and messages are being transmitted, increase the interval between
transmissions.
Meaning
A command that is not supported by the Unit has been used.
Processing
Check the contents of the command data.
Error code
Meaning
Remedy
08FF
Service not supported
Invalid service code or
instance ID
Check the service code and instance ID set-
tings.
16FF
Object does not exist
Invalid class ID
Check the class ID settings.
16FF
Device state conflict
A processing error has
occurred in the Tempera-
ture Controller.
Resend the DeviceNet explicit message.
0CFF
Object state conflict
A new command was
received while processing
the previous command.
Wait for a response to the command being
processed, and then send a new command.
Error code: 0204
Name: Busy error
No. of bytes
received
Source
MAC ID
End code
Read data
Note This data is valid only when using an
OMRON PC Master. If using a master
not manufactured by OMRON, refer to
the manual for that master.
No. of bytes
received
Source
MAC ID
End code
Note This data is valid only when using an
OMRON PC Master. If using a master
not manufactured by OMRON, refer to
the manual for that master.
Error code: 0401
Name: Undefined command