36
End Codes
Section 5-1
Meaning
The command is longer than the maximum permissible length.
Processing
Check the contents of the command data and re
-
enter it correctly.
Meaning
The command is shorter than the minimum permissible length.
Processing
Check the contents of the command data and re
-
enter it correctly.
Meaning
The number of data elements do not match the number of write data in the
command data.
Processing
Specify the command data so that the number of data elements match.
Meaning
The command format received is incorrect.
Processing
Check the communications conditions. If the communications conditions
match, there is a malfunction in the communications circuit at the Master Unit,
at the E5ZE, or at both Units.
Meaning
There is an error in the command data or the parameters are set outside the
permissible range.
Processing
Check the setting range and rewrite or reread the correct parameter values.
Meaning
The variable type code is set incorrectly.
Processing
Check the variable type code and re
-
enter it correctly.
Meaning
The first address in the command data is set incorrectly or the address is set
to words that do not exist in the set value and measurement value table.
Processing
Check the first address referring to the DeviceNet explicit messages set value
and measurement value table, and re
-
enter the correct address.
Error code: 1001
Name: Command length too long
Error code: 1002:
Name: Command length too short
Error code: 1003
Name: Number of data elements and data do not match
Error code: 1005
Name: FINS header error
Error code: 1100
Name: Parameter error
Error code: 1101
Name: Incorrect memory area
Error code: 1103
Name: First address outside range
Error code: 1104
Name: End address outside range