103
Alarm Mode Write: W#
Section 3-15
Communications Example
In this example, the E5ZE is operated with Output Operation Read (RU) under
the following conditions
Unit no.: 1
Control Points 0, 2, 4, and 6: Direct operation
Control Points 1, 3, 5, and 7: Reverse operation.
Command
Response
3-15 Alarm Mode Write: W#
Function
This command is used to designate the alarm mode of alarm 1 or 2 of a con-
trol point.
1.
Alarm Mode Write (W#) cannot be used at a control point in manual oper-
ation, control operation or auto
-
tuning operation.
2.
If the temperature control or manual operation at a control point is inter-
rupted, all the alarm output of the control point will be OFF.
Setting Data Range
@ 0 1 R U 0 0 0 0 4 6
s
*
@ 0 1 R U 0 0 0 0 5 5 4 6
s
Normal end
0 1 0 1 0 1 0 1
*
Bit status
Alarm
Alarm 1
Alarm 2
Default
00
Setting
code
Alarm OFF
00
Upper
-
and lower
-
limit alarm
01
Upper
-
limit alarm
02
Lower
-
limit alarm
03
Upper
-
and lower
-
limit range alarm
04
Upper
-
and lower
-
limit alarm with
standby sequence
05
Upper
-
limit alarm with standby
sequence
06
Lower
–
limit alarm with standby
sequence
07
Absolute
-
value upper
-
limit alarm
08
Absolute
-
value lower
-
limit alarm
09
Absolute
-
value upper
-
limit alarm
with standby sequence
0A
Absolute
-
value lower
-
limit alarm with
standby sequence
0B
HB and HS alarm
0C