65
Part 2
Serial Communications
This part of the manual provides information required to use RS-
232C communications through the RS-232C auxiliary setting jack on
the Temperature Controller
RS-232C Auxiliary Setting Jack and Remote I/O
Data written with the remote I/O function is updated in the E5ZE
every 200 ms. If different settings are made with the RS-232C
auxiliary setting jack and remote I/O communications, the settings
made with the RS-232C auxiliary setting jack will last only until the
next time the value is refreshed for remote I/O communications.
RS-232C Auxiliary Setting Jack and FINS Messages
Data written for the RS-232C auxiliary setting jack and FINS mes-
sage are both achieved using commands If different settings are
made with the RS-232C auxiliary setting jack and a FINS mes-
sage, the last command that was executed will determine the
value of the setting.
Saving Set Values
Any data sent with DeviceNet is automatically saved and will
remain in memory even if the power supply is turned OFF. Data
set from the RS-232C auxiliary setting jack, however, will not be
saved unless the Memory Write Command (WE) is executed
before power is turned OFF.