29
DeviceNet Explicit Messages Set Values and Measurement
Section 4-4
Variable Type: 88
• Set the values of X and Y in the addresses as follows:
X: Control point number (0 to 7). Set
“
A
”
for all control points.
Y:
Memory bank number (0 to 7). Set
“
8
”
for the current memory bank or
“
A
”
for all memory banks. The setting A is valid for writing only.
X and Y cannot both be set to A at the same time.
Example: To set the alarm 1 temperature in memory bank 3 for control
point 5, the address would be 5301 (hex).
•
Set values cannot be written while auto
-
tuning is being executed.
No.
Address
Set value or measurement value
Default
Data setting or monitoring range
Data type
1
XY00
Set point (read only)
0000
Depends on the input type and setting
unit. (Refer to page 25.)
Numeric
Read/write
2
XY01
Alarm 1 temperature (See note 1.) 0000
Depends on setting unit. (Refer to
page 25.)
3
XY02
Alarm 2 temperature (See note 1.) 0000
4
XY03
Proportional band
0000
Range: 0000 to 270F (0.0 to 999.9)
Unit:
0.1
°
C/
°
F
5
XY04
Integral time
0000
Range: 0000 to 0F9F (0 to 3999)
Unit:
1 s
6
XY05
Derivative time
0000
7
XY06
Heating hysteresis
See note
3
Range: 0000 to 03E7 (0.0 to 99.9)
Unit:
0.1
°
C/
°
F
8
XY07
Input shift value
0000
Range: FC19 to 03E7 (-99.9 to 99.9)
Unit:
0.1
°
C/
°
F
9
XY08
Heater burnout detection current
0000
Range: 0000 to 01F4 (0.0 to 50.0)
Unit:
0.1 A
10
XY09
Control period (heating)
0002
Range: 0001 to 0063 (0 to 99)
Unit:
1 s
11
XY0A
Manual reset value
01F4
Range: 0000 to 03E8 (0.0 to 100.0)
Unit:
0.1%
12
XY0B
Heating output variable lower limit
0000
13
XY0C
Heating output variable upper limit 03E8
14
XY0D
Ramp value (See note 1.)
0000
Range: 0000 to 03E7 (0.0 to 99.9)
Unit:
0.1
15
XY0E
Ramp time unit (See note 1.)
0000
0000: s, 0001: min, or 0002: hr
16
XY0F
Output variable change rate limit
0000
Range: 000 to 03E8 (0.0 to 100.0)
Unit:
0.1% per sampling period
17
XY10
Dead band
0000
Range: FC19 to 03E7 (-999 to 999)
Unit:
1
°
C/
°
F
18
XY11
Cooling coefficient
000A
Range: 0000 to 0064 (0.0 to 10.0)
Unit:
0.1
19
XY12
Cooling hysteresis
See note
3
Range: 0000 to 03E7 (0.0 to 99.9)
Unit:
0.1
°
C/
°
F
20
XY13
Cooling control period
0002
Range: 0001 to 0063 (0 to 99)
Unit:
1 s
21
XY14
Cooling output variable lower limit
0000
Range: 0000 to 03E8 (0.0 to 100.0)
Unit:
0.1%
22
XY15
Cooling output variable upper limit
03E8
23
XY16
Fuzzy strength
0032
Range: 0000 to 0063 (0 to 99)
Unit:
1%
24
XY17
Fuzzy scale 1
270F
Range: 0002 to 270F (0.2 to 999.9)
Unit:
0.1
°
C/
°
F
25
XY18
Fuzzy scale 2
270F
Range: 0014 to 270F (0.20 to 99.99)
Unit:
0.01