28
DeviceNet Explicit Messages Set Values and Measurement
Section 4-4
5.
When the Initializing Setting Data command is executed, the parameters
in the storage area will be reset to the factory
-
set default values even if the
E5ZE is in RAM write mode.
6.
Set the Temperature Control Start/Stop Bit for the applicable control point
to 1 before starting manual operation. (Refer to the graph in the next sec-
tion.)
4-4-4
Relationship between Operating Status and Operating
Commands
The relationship between operating commands from the remote I/O Tempera-
ture Control Start/Stop Bit and operating commands from DeviceNet explicit
messages or the RS
-
232C auxiliary setting jack is represented in the following
graph. Remote I/O data is refreshed every 200 ms. Operating commands that
are different from the status of the remote I/O Temperature Control Start/Stop
Bit will, therefore, be momentarily effective and will then immediately change
to the commands from the remote I/O.
4-4-5
Set Values in Memory Banks
The following variable type table shows the information required to monitor or
change the settings for the control points in memory banks 0 to 7.
E5ZE status
Operation stop
Remote I/O
Temperature Control
Start/Stop Bit status
Bit 0
®
1
Bit 1
®
0
Bit 0
®
1
Bit 1
®
0
Manual Operation Start
Command executed
Manual Operation Start
Command executed
Manual Operation Start
Command executed
Temperature Control
Start Command
executed
Temperature Control
Start Command
executed
Temperature control
Manual operation