V7-RTS INSTRUCTIONS 

Page 1 of 5 

 

DESCRIPTION: 

The V7-RTS is a controller for filtration & heating of a swimming pool with a solar collector. Two pumps are controlled 

and the solar pump can be locked to the filtration pump if required for retrofit/integrated plumbing.   

 

INSTALLATION INSTRUCTIONS: 

CONTROLLER MOUNTING: 

Find a suitable location to mount the control box. Ideally as with all pool equipment it should be installed out of direct 

weather  and  no  closer  than  3  meters  from  the  water’s  edge  and  a  minimum  600mm  of  the  ground.  Lift  up  the  two 

mounting tabs and use two appropriate screws to mount the control box to the wall, keeping in mind that the power 

cable is 1.8m long and should be plugged directly into a general power outlet, not into an extension lead. 

 

TEMPERATURE SENSORS: 

The pool sensor must be fitted into the heating circuit, as close to the pool as practical, preferably in a position out of 

direct sunlight. It is recommended that a 14.5mm hole be drilled in the side of the PVC pipe (not the top of the pipe 

where water will collect), this can be carried out using a Dontek PD01 grinding drill or a small pilot hole can be drilled 

with a 14.0mm drill-bit used spinning in a counter clockwise direction to minimize the chance of shattering pipe. Insert 

the grommet into the pipe and gently push in the sensor barb. Ideally ~30cm of the cable from the sensor should be tied 

to the shaded side of the pipe to prevent extreme ambient conditions leeching into the sensor via the copper in the 

cable. The blue sensor plug is to be fitted to the plug socket marked POOL. 

The roof sensor must be fitted into a small piece of rubber collector material away from the main collector but on the 

same aspect, preferably no more than 50cm from the roof gutter (for ease of sensor replacement). If required the roof 

sensor  can  be  on  a  different  roof  as  the  solar  collector  as  long  as  the  alignment  to  the  sun  is  similar  to  the  solar 

collector.  For  encapsulated  collector  panels  use  the  manufacturer’s  instructions  for  roof  sensor  placement.  The  red 

sensor plug is to be fitted to the plug socket marked ROOF. 

SENSOR NOTES: 

All excess cable must be removed; coils of cable are not permitted under any circumstances and 

must 

not

 be tied to or near 240V wiring. If the cable is to be extended with non genuine cable a size of 14/020 should be 

used. 

Any cable joins must be soldered and

 

this includes where the cable enters the terminal block at the case base

Heat shrink is to be used over soldered joints to eliminate moisture ingress. If the cable end is to be refitted to the plug 

sockets then the polarity must be observed as incorrect polarity will show as a short circuit fault on the LCD screen. The 

sensor cable with the thin white trace (or red wire) is the positive and should be fitted to the right hand cable entry 

when the screws are in  a vertical position. Once cables have been  correctly fitted the unit can  be turned  on. Do not 

allow any joins in the cable to be underground. 

 

PUMP CONNECTIONS: 

The pool filtration pump plugs into the 240V socket labelled AUX. PUMP. 

The solar collector pump plugs into the 240V socket labelled SOLAR PUMP. 

The maximum combined load for both sockets is 9.98 AMPS at 2395W. 

 

OPERATING INSTRUCTIONS: 

 

The controller always starts in automatic mode of operation. To change settings enter the SETTINGS MENU by pushing 

either the 

Up

 or 

Down

 SETTINGS

 

buttons and the following will be displayed; 

 

 

The menu system can be navigated using the 

Up & Down

 SETTINGS buttons, all selectable and changeable values will 

flash on the LCD screen. Use the 

ENTER/MANUAL

 button to accept the currently displayed (flashing) item. 

 

All menu items are shown below; 

 

 

 

Summary of Contents for V7-RTS

Page 1: ...rably no more than 50cm from the roof gutter for ease of sensor replacement If required the roof sensor can be on a different roof as the solar collector as long as the alignment to the sun is similar to the solar collector For encapsulated collector panels use the manufacturer s instructions for roof sensor placement The red sensor plug is to be fitted to the plug socket marked ROOF SENSOR NOTES ...

Page 2: ...erature menu is selected the following is displayed Adjusting the temperature limit will allow the controller to heat pool until the temperature limit C is achieved heating will then remain off until the sample wait period expires if no sample wait period is active the heating will remain off until the pool temperature drops C below the temperature limit setting due to rounding the actually heatin...

Page 3: ...p select independent std if the solar system and heater are plumbed separate from the filtration line See images below for typical set ups Warn the customer not to change from series retro fit as damage may occur If NO is selected then the solar pump will stop if solar heating is no longer required If YES is selected the follow menu is presented The controller stops all pumps for the selected numb...

Page 4: ...al of 4 C Minimum Roof of 20 C Freeze protect is OFF Boil protect is OFF 6 SAVE EXIT When this menu is selected push the ENTER MANUAL button to save ALL settings the controller will then return to automatic operation Note If any of the menu items are left unattended for 3 minutes the menu will time out and automatically save all settings and return to automatic operation The ENTER MANAL button Pre...

Page 5: ...r s instruction may void the warranty Valves and actuators are covered by a twelve month warranty at the discretion of their manufacturer Warranty does not cover travel costs to or from installation site If the power cord is damaged do not use the controller return the unit to the supplier for repair Customer Record To be retained by the customer Dealer Installer Name _____________________________...

Page 6: ...rably no more than 50cm from the roof gutter for ease of sensor replacement If required the roof sensor can be on a different roof as the solar collector as long as the alignment to the sun is similar to the solar collector For encapsulated collector panels use the manufacturer s instructions for roof sensor placement The red sensor plug is to be fitted to the plug socket marked ROOF SENSOR NOTES ...

Page 7: ...erature menu is selected the following is displayed Adjusting the temperature limit will allow the controller to heat pool until the temperature limit C is achieved heating will then remain off until the sample wait period expires if no sample wait period is active the heating will remain off until the pool temperature drops C below the temperature limit setting due to rounding the actually heatin...

Page 8: ...p select independent std if the solar system and heater are plumbed separate from the filtration line See images below for typical set ups Warn the customer not to change from series retro fit as damage may occur If NO is selected then the solar pump will stop if solar heating is no longer required If YES is selected the follow menu is presented The controller stops all pumps for the selected numb...

Page 9: ...al of 4 C Minimum Roof of 20 C Freeze protect is OFF Boil protect is OFF 6 SAVE EXIT When this menu is selected push the ENTER MANUAL button to save ALL settings the controller will then return to automatic operation Note If any of the menu items are left unattended for 3 minutes the menu will time out and automatically save all settings and return to automatic operation The ENTER MANAL button Pre...

Page 10: ...r s instruction may void the warranty Valves and actuators are covered by a twelve month warranty at the discretion of their manufacturer Warranty does not cover travel costs to or from installation site If the power cord is damaged do not use the controller return the unit to the supplier for repair Customer Record To be retained by the customer Dealer Installer Name _____________________________...

Reviews: