background image

INSTALLATION-and OPERATION MANUAL 

ELECTRIC ACTUATOR AE04-AE19 STANDARD DESIGN

 

 

 

 

 

MANUAL 

 

Phone 

+49 (0)7181-404 0 

 

 

 

WESA-Armaturen GmbH 

ELECTRIC ACTUATOR 

 

Telefax 

+49 (0)7181-404-33 

Spanninger Straße 5 

AE04 |AE19 

 

mailto: 

[email protected] 

73650 Winterbach 

STATUS 03-2022 

Page

 1

 

 

http 

www.wesa-armaturen.de 

Deutschland 

 

ELECTRIC ACTUATORS 

AE04-AE19 STANDARD DESIGN 

 

 

DESCRIPTION| | GENERAL DATA

 

o

 

Standard electric actuator for open-close operation with 90° actuating angle 

o

 

Aluminum die-cast housing 

o

 

Electrical connection via terminal box and 2 cable glands 

o

 

2 selectable voltages: 230V AC and 24V DC 

o

 

2 adjustable motor limit switches for 0°-90° rotation 

o

 

2 potential-free feedback contacts 

o

 

Position feedback *Open* *Close* o Temperature range 

o

 

Temperature range -30°C to +60°C 

o

 

Bimetal overload protection (>125°C) 

o

 

Protection class IP67 

o

 

Position indicator with scale 

o

 

Manual override 

 

 

These  operating  instructions  contain  important  information  concerning  the 
installation,  function,  maintenance  and  storage  of  the  WESA  electric 
actuators. Please read them thoroughly and keep them for any queries. Only 
instructed and qualified personnel should service these actuators. 
 

CAUTION! 

If the following and warning notes are not followed, hazards could result and 
the distributor's warranty could become invalid. The distributor is available 
for any queries

 

 

 

Summary of Contents for AE04

Page 1: ...ges 230V AC and 24V DC o 2 adjustable motor limit switches for 0 90 rotation o 2 potential free feedback contacts o Position feedback Open Close o Temperature range o Temperature range 30 C to 60 C o Bimetal overload protection 125 C o Protection class IP67 o Position indicator with scale o Manual override These operating instructions contain important information concerning the installation funct...

Page 2: ...90 0 90 0 90 0 90 0 90 0 90 Current consumption 0 16 A 1 28 A 0 16 A 1 28 A 0 16 A 0 35 A 2 03 A 0 37 A 3 57 A Power consumption 10W 13 W 10 W 13 W 10 W 25 W 25 W 40 W 35 W Weight kg approx 2 0 2 0 2 0 2 0 2 0 3 0 3 0 8 0 8 0 Dimensions mm 160x137x133 196x145x158 255x182x196 ISO Flange F03 F05 F07 F05 F07 F07 F010 Adapter Coupling 9 mm 11 mm 14 mm 17 mm 22 mm Technische Daten AE 13 AE14 AE15 AE16 ...

Page 3: ...one 49 0 7181 404 0 WESA Armaturen GmbH ELECTRIC ACTUATOR Telefax 49 0 7181 404 33 Spanninger Straße 5 AE04 AE19 mailto info wesa armaturen de 73650 Winterbach STATUS 03 2022 Page 3 http www wesa armaturen de Deutschland CONNECTION DIAGRAM Electric actuator with terminal box 230V AC 50Hz ...

Page 4: ...hone 49 0 7181 404 0 WESA Armaturen GmbH ELECTRIC ACTUATOR Telefax 49 0 7181 404 33 Spanninger Straße 5 AE04 AE19 mailto info wesa armaturen de 73650 Winterbach STATUS 03 2022 Page 4 http www wesa armaturen de Deutschland CONNECTION DIAGRAM TYPE Electric actuator with terminal box 24V DC ...

Page 5: ...efore any intervention on the electric actuator o Any intervention must be carried out only by a qualified electrician or by personnel trained according to the rules of electrical engineering safety and all other applicable standards o It is essential to follow the sequence of instructions for connection and commissioning described in these instructions otherwise proper functioning is not guarante...

Page 6: ...ubber cover of the manual override o Insert the hexagonal key into the manual override o Using the hexagonal wrench turn the actuator to the desired position proceeding as follows o Use the position indicator to determine which position the actuator is in RED AREA ACTUATOR CLOSED ZU SHUT YELLOW GREEN AREA ACTUATOR OPEN AUF OPEN RED YELLOW RED GRÜN AREA IN AN INTERMEDIATE POSITION BETWEEN OPEN AND ...

Page 7: ... the actuator please proceed as follows o Switch off the power supply to the actuator o Turn the actuator with the manual override to the closed position of your valve o Open the upper cover with the position indicator by loosening the 4 screws o Adjust the desired position by turning the cam D1 with the set screw CLOSED red clockwise until it audibly actuates the limit switches K1 and K2 Fig 1 o ...

Page 8: ...ct the power supply at the actuator o Loosen the 4 screws on the cover of the position indicator and remove it o Turn the actuator completely to the CLOSED position using the manual override until the CLOSED limit switch is audibly actuated o Loosen the locking nut of the mechanical stop for the CLOSED position Fig 2 o Turn the adjusting screw for the CLOSED position in with an Allen key until it ...

Reviews: