APP - 10
APPENDICES
Table 1.1 Servo program setting error list (Continued)
Error code
stored in SD517
Error name
Error contents
Error processing
Corrective action
903
Start error
A virtual mode program was
started in the real mode.
Check the program mode
allocation.
(1) Operation disable instructions
(VPF, VPR, VPSTART, PVF,
PVR, ZERO, VVF, VVR, OSC)
was started in virtual mode.
(2) Operation disable instructions
(ZERO, OSC, CHGA-C) was
started in real mode axis.
Correct the servo program.
905
Start error
(3) Operation disable instructions
(CHGA-C, CHGA-E) from the
D(P).SVST instruction of
Motion dedicated instruction
was started.
Use the D(P).CHGA instruction
of Motion dedicated instruction.
(1) Unused axis of the system
setting is set in the servo
program start.
(2) It was started by setting the
real mode axis in the virtual
servo program.
(3) It was started in the condition
that the real mode axis had
been mixed with virtual axis in
the interpolation axis.
906
Axis No. setting
error
(4) It was started by setting the
virtual axis in the real mode
program in virtual mode.
Set the axis No. set in the
system setting or mechanical
system program.
907
Start error
It was started during processing
for switching from real mode to
virtual mode.
908
Start error
It was stated during processing for
switching from virtual mode to real
mode.
Positioning control does not
start.
Use M2043 (real mode/virtual
mode switching request),
M2044 (real mode/virtual
mode switching status) as
interlocks for start.
Содержание Q Series
Страница 1: ......
Страница 19: ...A 18 MEMO ...
Страница 129: ...4 90 4 POSITIONING DEDICATED SIGNALS MEMO ...
Страница 134: ...5 5 5 MECHANICAL SYSTEM PROGRAM MEMO ...
Страница 139: ...5 10 5 MECHANICAL SYSTEM PROGRAM MEMO ...
Страница 163: ...6 24 6 DRIVE MODULE MEMO ...
Страница 201: ...7 38 7 TRANSMISSION MODULE MEMO ...
Страница 257: ...9 12 9 REAL MODE VIRTUAL MODE SWITCHING AND STOP RE START MEMO ...
Страница 267: ...10 10 10 AUXILIARY AND APPLIED FUNCTIONS MEMO ...
Страница 352: ......