11 OPTIONS AND PERIPHERAL EQUIPMENT
11.5 FR-CV-(H) power regeneration common converter
377
11
Other precautions
• When using the FR-CV-(H), always install the dedicated stand-alone reactor (FR-CVL-(H)). Do not use the power factor
improving AC reactor (FR-HAL-(H)) or power factor improving DC reactor (FR-HEL-(H)).
• The inputs/outputs (main circuits) of the FR-CV-(H) and servo amplifiers include high-frequency components and may
provide electromagnetic wave interference to communication equipment (such as AM radios) used near them. In this case,
interference can be reduced by installing the radio noise filter (FR-BIF(-H)) or line noise filter (FR-BSF01, FR-BLF).
• The overall wiring length for connection of the DC power supply between the FR-CV-(H) and servo amplifiers should be 5 m
or less, and the wiring must be twisted.
Specifications
*1 This is the time when the protective function of the FR-CV-(H) is activated. The protective function of the servo amplifier is activated in
the time indicated in the following section.
Page 311 Overload protection characteristics
*2 The specified value is the power supply capacity of FR-CV-(H). The total power supply capacities of the connected servo amplifiers are
actually required.
Item
Power regeneration common converter
FR-CV-_
7.5K
11K
15K
22K
30K
37K
55K
Total of connectable servo amplifier capacities
[kW]
3.75
5.5
7.5
11
15
18.5
27.5
Maximum servo amplifier capacity [kW]
3.5
5
7
11
15
15
22
Output
Total of connectable servo motor
rated currents [A]
33
46
61
90
115
145
215
Regenerative
braking torque
Short-time
rating
Total capacity of applicable servo motors, 300% torque, 60 s
Continuous
rating
100% torque
Power
Rated input AC voltage/frequency
3-phase 200 V AC to 220 V AC, 50 Hz, 200 V AC to 230 V AC, 60 Hz
Permissible AC voltage
fluctuation
3-phase 170 V AC to 242 V AC, 50 Hz, 170 V AC to 253 V AC, 60 Hz
Permissible frequency fluctuation
5%
Power supply capacity
[kVA]
17
20
28
41
52
66
100
IP rating (JEM 1030), cooling method
Open type (IP00), forced cooling
Environment
Ambient temperature
-10
to 50
(non-freezing)
Ambient humidity
5 %RH to 90 %RH (non-condensing)
Ambience
Indoors (no direct sunlight), free from corrosive gas, flammable gas, oil mist, dust, and dirt
Altitude, vibration resistance
1000 m or less above sea level, 5.9 m/
Molded-case circuit breaker or earth-leakage
current breaker
30AF
30A
50AF
50A
100AF
75A
100AF
100A
125AF
125A
125AF
125A
225AF
175A
Magnetic contactor
S-N20
S-T21
S-N35
S-T35
S-N50
S-T50
S-N65
S-T65
S-N80
S-T80
S-N95
S-T100
S-N125