374
11 OPTIONS AND PERIPHERAL EQUIPMENT
11.5 FR-CV-(H) power regeneration common converter
■
400 V class
When using the servo amplifier of 7 kW or less, be sure to disconnect the wiring of built-in regenerative
resistor (3.5 kW or less: P+ and D, 5 kW/7 kW: P+ and C).
*1 Configure a sequence that will shut off main circuit power in the following.
An alarm occurred at FR-CV-H or servo amplifier.
EM1 (Forced stop 1) is enabled.
*2 For the servo amplifier, configure a sequence that will switch the servo-on after the FR-CV-H is ready.
*3 Configure a sequence that will make a stop with the emergency stop input of the controller if an alarm occurs in the FR-CV-H. When the
controller does not have an emergency stop input, use the forced stop input of the servo amplifier to make a stop as shown in the
diagram.
*4 When using FR-CV-H, always disconnect wiring between P3 and P4 terminals.
*5 Set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1).
*6 When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker.
*7 The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they can be
configured by one.
MC
MCCB
3-phase
380 V AC
to
480 V AC
FR-CVL-H
RA2
RA1
EM1 OFF
ON
*1
SK
RA1
*3
EM1
R2/L1
S2/L2
N/L-
*2
P24
SD
RDYB
RDYA
SE
P/L+
T2/L3
R/L11
S/L21
T/MC1
*1
L11
L21
P4
N-
U
V
W
EM1
*1*5
U
V
W
CN2
FR-CV-H
Servo motor
Servo amplifier
Controller
*4
*6
B
C
A
24 V DC
*7
24 V DC
*7
ALM
24 V DC
*7
Step-down
transformer