4 STARTUP
4.3 Switch setting and display of the servo amplifier
135
4
Scrolling display
Station number will be displayed in hexadecimal.
Normal display
When there is no alarm, the station No. is displayed.
Alarm display
When an alarm occurs, the alarm number (two digits) and the alarm detail (one digit) are displayed following the status
display. For example, the following shows when [AL. 32 Overcurrent] is occurring.
If an alarm occurs during initial communication through a network, the status, the alarm number (two digits) and alarm detail
(one digit), and the network initial communication status are displayed, in that order. For example, the following shows when
[AL. 16.1 Encoder initial communication - Receive data error 1] is occurring.
Status
(1 digit)
Station No.
(2 digits)
"b"
"C"
"d"
: Indicates ready-off and servo-off status.
: Indicates ready-on and servo-off status.
: Indicates ready-on and servo-on status.
Status
After 0.8 s
Alarm No.
After 0.8 s
Blank
After 0.2 s
Status
(1 digit)
Station No.
(2 digits)
"n": Indicates that an alarm is occurring.
Alarm detail
(1 digit)
Alarm No.
(2 digits)
Status
After 0.8 s
Alarm No.
After 0.8 s
Blank
After 0.2 s
Status
(1 digit)
Station No.
(2 digits)
"n": Indicates that an alarm is occurring.
Alarm detail
(1 digit)
Alarm No.
(2 digits)
After 0.2 s
Network initial
communication
status
After 1.6 s
Blank