11 OPTIONS AND PERIPHERAL EQUIPMENT
11.10 Molded-case circuit breakers, fuses, magnetic contactors
405
11
*1 When having the servo amplifier comply with the IEC/EN/UL/CSA standard, refer to the following.
Page 572 Compliance with global standards
*2 Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80
ms or less.
*3 Use a molded-case circuit breaker which has the same or higher operation characteristics than our lineup.
*4 S-N18 can be used when auxiliary contact is not required.
The Type E Combination motor controller can also be used instead of a molded-case circuit breaker.
*1 The values of the SCCR vary depending on the combination with the servo amplifier.
*2 1-phase input is not supported.
MR-J4-60GF4(-RJ)
30 A frame 5 A
30 A frame 5 A
480
T
10
600
S-N10
S-T10
MR-J4-100GF4(-RJ)
30 A frame 10 A
30 A frame 5 A
15
MR-J4-200GF4(-RJ)
30 A frame 15 A
30 A frame 10 A
25
MR-J4-350GF4(-RJ)
30 A frame 20 A
30 A frame 15 A
35
S-N20
S-T21
MR-J4-500GF4(-RJ)
30 A frame 20 A
30 A frame 20 A
50
MR-J4-700GF4(-RJ)
30 A frame 30 A
30 A frame 30 A
65
S-N20
S-T21
MR-J4-11KGF4(-RJ)
50 A frame 50 A
50 A frame 50 A
100
S-N25
S-T35
MR-J4-15KGF4(-RJ)
60 A frame 60 A
60 A frame 60 A
150
S-N35
S-T35
MR-J4-22KGF4(-RJ)
100 A frame 100 A
100 A frame 100 A
175
S-N50
S-T50
MR-J4-10GF1(-RJ)
30 A frame 5 A
30 A frame 5 A
240
10
300
S-N10
S-T10
MR-J4-20GF1(-RJ)
30 A frame 10 A
30 A frame 10 A
15
MR-J4-40GF1(-RJ)
30 A frame 15 A
30 A frame 10 A
20
Servo amplifier
Rated input
voltage AC [V]
Input phase
Type E Combination motor controller
SCCR [kA]
Model
Rated voltage
AC [V]
Rated current
[A] (Heater
design)
MR-J4-10GF(-RJ)
200 to 240
3-phase
MMP-T32
240
1.6
50
MR-J4-20GF(-RJ)
2.5
MR-J4-40GF(-RJ)
4
MR-J4-60GF(-RJ)
6.3
MR-J4-70GF(-RJ)
6.3
MR-J4-100GF(-RJ)
8
MR-J4-200GF(-RJ)
18
MR-J4-350GF(-RJ)
25
25
MR-J4-500GF(-RJ)
32
MR-J4-60GF4(-RJ)
380 to 480
3-phase
480Y/277
2.5
50
MR-J4-100GF4(-RJ)
4
MR-J4-200GF4(-RJ)
8
MR-J4-350GF4(-RJ)
13
MR-J4-500GF4(-RJ)
18
MR-J4-700GF4(-RJ)
25
25
Servo amplifier
Molded-case circuit breaker
*1*3
Fuse
Magnetic
contactor
*2
Frame, rated current
Voltage AC [V]
Class
Current [A] Voltage AC
[V]
Power factor
improving
reactor is not
used
Power factor
improving
reactor is used