5 PARAMETERS
5.2 Detailed list of parameters
PA02
**REG
Regenerative option
_ _ x x
Regenerative option
Select a regenerative option.
Incorrect setting may cause the regenerative option to burn.
If a selected regenerative option is not for use with the servo amplifier, [AL. 37 Parameter error] occurs.
00: Regenerative option is not used.
• For the servo amplifiers of 100 W, a regenerative resistor is not used.
• For servo amplifier of 0.2 kW to 7 kW, built-in regenerative resistor is used.
• Supplied regenerative resistors or regenerative option is used with the servo amplifier of 11 kW to 22 kW.
01: FR-RC-(H)/FR-CV-(H)/FR-BU2-(H)
• When you use FR-RC-(H) or FR-CV-(H), select "1" of "[AL. 10 Undervoltage] detection method selection"
in [Pr. PC20].
02: MR-RB032
03: MR-RB12
04: MR-RB32
05: MR-RB30
06: MR-RB50 (Cooling fan is required.)
08: MR-RB31
09: MR-RB51 (Cooling fan is required.)
0B: MR-RB3N
0C: MR-RB5N (Cooling fan is required.)
80: MR-RB1H-4
81: MR-RB3M-4 (Cooling fan is required.)
82: MR-RB3G-4 (Cooling fan is required.)
83: MR-RB5G-4 (Cooling fan is required.)
84: MR-RB34-4 (Cooling fan is required.)
85: MR-RB54-4 (Cooling fan is required.)
91: MR-RB3U-4 (Cooling fan is required.)
92: MR-RB5U-4 (Cooling fan is required.)
FA: When the supplied regenerative resistors or the regenerative option is cooled by the cooling fan to
increase the ability with the servo amplifier of 11 kW to 22 kW.
00h
_ x _ _
For manufacturer setting
0h
x _ _ _
0h
PA03
*ABS
Absolute position
detection system
_ _ _ x
Absolute position detection system selection
Set this digit when using the absolute position detection system.
0: Disabled (incremental system)
1: Enabled (absolute position detection system)
The absolute position detection system cannot be used when an incremental type linear encoder is used or
the semi closed loop/fully closed loop switching is enabled. Enabling the absolute position detection system
will trigger [AL. 37].
0h
_ _ x _
For manufacturer setting
0h
_ x _ _
0h
x _ _ _
0h
No./symbol/
name
Setting
digit
Function
Initial
value
[unit]