Drive A1 Submenu
51
Parameter
[
Alphanumeric]
Description
Units
Range
Default
Hidden
Item
Run
lockout
ENGLISH
(U3)
METRIC
(U3)
Ser2 Flt Tol
[A168]
(Serial Mode 2 Fault Tolerance)
Used only
with custom serial protocol (mode 2)
When
in Serial Mode 2, this parameter defines the
maximum time that may elapse between
valid run time messages while in serial run
mode before a serial fault is declared.
sec
0.00
– 2.00
0.50
Y
Y
Mains Dip
Speed
[A169]
(Mains Dip Speed Multiplier) This parameter
sets a limit on the speed the drive will turn
the motor, as a percentage of contract
speed. The Mains Dip function is enabled
by the Mains Dip Enable (MAINS DIP
ENA(C1)) parameter. When the drive goes
into ‘low voltage’ mode, it limits the speed to
the percentage defined by this parameter.
‘Low voltage’ mode is defined as when the
drive declares a UV alarm, which is defined
by the Input line-to-line voltage (INPUT L-L
VOLTS(A4)) parameter and the
Undervoltage Alarm Level (UV ALARM
LEVEL(A4)).
%
5.00
– 99.99
25.00
Y
N
Mspd
Delay 1
[A170]
(Multi-Step Speed Delay 1) Determines the
recognition time delay for a defined multi-step
speed command. For more information, see
p. 59.
sec
0.000
– 10.000
0.000
Y
Y
Mspd
Delay 2
[A171]
(Multi-Step Speed Delay 2) Determines the
recognition time delay for a defined multi-step
speed command. For more information, see
p. 59.
sec
0.000
– 10.000
0.000
Y
Y
Mspd
Delay 3
[A172]
(Multi-Step Speed Delay 3) Determines the
recognition time delay for a defined multi-step
speed command. For more information, see
p. 59.
sec
0.000
– 10.000
0.000
Y
Y
Mspd
Delay 4
[A173]
(Multi-Step Speed Delay 4) Determines the
recognition time delay for a defined multi-step
speed command. For more information, see
p. 59.
sec
0.000
– 10.000
0.000
Y
Y
Mid Speed
Lvl
[A174]
(Mid Speed Level) This parameter sets the
level/threshold for mid speed detection. This
is only used to generate the mid speed logic
output. Units in percent of contract speed.
%
0.00
– 110.00
80.00
Y
Y
Encdr Flt
Sense
ii
[A175]
(Encoder Fault Sensitivity
ii
) Determines the
percentage of voltage rise to occur before an
Encoder Fault occurs due to voltage rise at
the beginning of run. Units in percent of
Rated Mtr Volts (A5)
%
ii
10
– 100
ii
30
ii
N
ii
Y
ii
ARB
Advance
i,ii
[A176]
(Anti-Rollback Advance time
i,ii
)
Set to the amount of time from when the
drive detects motion to when the brake is
opened.
Used with ARB Select (C1) set to
ARB2 or ARB3.
sec
i,ii
0.00 - 2.00
i,ii
0.30
i,ii
N
i,ii
Y
i,ii
ARB
Decay
i,ii
[A178]
(Anti-Rollback Decay time
i,ii
)
Stabilization period after ARB advance.
Typical value is 0.2s to 0.4s
Used with ARB
Select (C1) set to ARB2 or ARB3
sec
i,ii
0.00 - 2.00
i,ii
0.20
i,ii
N
i,ii
Y
i,ii
i
Parameter accessible through
CLOSED LOOP (U9)
Operation
ii
Parameter accessibly through
PM (U9)
Operation
iii
Parameter accessible through
OPEN LOOP(U9)
Operation
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......