Drive A1 Submenu
41
Parameter
[
Alphanumeric]
Description
Units
Range
Default
Hidden
Item
Run
lockout
ENGLISH
(U3)
METRIC
(U3)
Regen
Torq Limit
[A108]
(Regenerating Current Limit) This
parameter sets the maximum amount of
regenerative torque the drive will see during
regeneration. This parameter may need
adjustment to reduce the effects of field
weakening. Units in percent of rated torque.
Note: The Torque Limit LED will be lit once
the limit defined by this parameter is
reached.
%
0.0
– 275.0
200.0
N
N
Flux Wkn
Factor
i
[A109]
(Flux Weakening Factor
i
) This parameter
limits the maximum amount of torque
available at higher speeds. When the drive
is commanding higher speeds, this
parameter defines a percentage of the
defined torque limits (MTR TORQUE LIMIT
and REGEN TORQ LIMIT). This parameter
is used to reduce the effects of field
weakening and reduce the amount of motor
current produced at higher speeds. Units in
percent of torque.
For further information, see page 54.
%
i
60
– 100
i
100
i
Y
i
N
i
Trq Lim
Msg Dly
[A110]
(Torque Limit Message Delay) This
parameter determines the amount of time
the drive is in torque limit before the “HIT
TORQUE LIMIT
” alarm message is
displayed.
sec
0.00
– 10.00
0.50
2.00
Y
Y
Gain
Reduce
Mult
i,ii
[A111]
(Gain Reduce Multiplier
i,ii
) This parameter
is the percent of ‘response’ the speed
regulator should use in the ‘low gain’ mode.
This value reduces the RESPONSE value
when the drive is in ‘low gain’ mode. (i.e.
setting this parameter to 100% equals no
reduction in gain in the ‘low gain’ mode).
See GAIN CHNG LEVEL on page 55.
%
i,ii
10
– 100
i,ii
100
i,ii
Y
i,ii
N
i,ii
Gain Chng
Level
i,ii
[A112]
(Gain Change Level
i,ii
) This parameter sets
the speed level to change to low gain mode
(only with internal gain switch). See GAIN
CHNG LEVEL on page 55. Units in
percent of rated speed.
%
i,ii
0.0
– 100.0
i,ii
100.0
i,ii
Y
i,ii
N
i,ii
Spd Dev Hi
Level
i
[A113]
(Speed Deviation High Level
i
) This
parameter sets the level at which a speed
deviation alarm will be declared. For more
information, see SPD DEVIATION on page
56.
%
i
0.0
– 99.9
i
10.0
i
Y
i
N
i
Ramped
Stop Time
i,ii
[A114]
(Ramped Stop Time
i,ii
) Time to ramp torque
from rated torque to zero. Note: this
parameter is used only with torque ramp
down stop function. For more information
see RAMPED STOP TIME on page 56.
sec
i,ii
0.00
– 2.50
i,ii
0.20
i,ii
0.50
i,ii
Y
i,ii
N
i,ii
i
Parameter accessible through
CLOSED LOOP (U9)
Operation
ii
Parameter accessibly through
PM (U9)
Operation
iii
Parameter accessible through
OPEN LOOP(U9)
Operation
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......