User Switches C1 Submenu
83
Parameter
[Alphanumeric]
Description
Choices
Default
Hidden
item
Run
lockout
ENGLISH
(U3)
METRIC
(U3)
Brake Pick
Src
[C116]
(Brake Pick Source)
If the BRAKE PICK SRC (C1) is set to
INTERNAL, the HPV 900 Series 2 will
attempt to pick (lift) the brake when
magnetizing current has been developed
in the motor.
internal
[1]
serial
[2]
INTERNAL
Y
Y
Brake Pick
Cnfm
[C117]
(Brake Pick Confirm)
If this switch is set to EXTERNAL TB, the
HPV 900 Series 2 will wait for brake pick
confirmation before releasing the speed
reference. When set to EXTERNAL TB,
the MECH BRK PICK signal on TB1 must
also be selected.
none
[0]
external tb
[1]
internal time
[2]
NONE
Y
Y
Motor Ovrld
Sel
[C118]
(Motor Overload Select)
This parameter selects the action to be
taken by drive when declaring a user
selectable Motor Overload. When the
motor overload level is reached, the
options are:
Alarm
– the drive only declares a
motor overload and the user is
responsible for action
Flt immediate
– the drive will
immediately declare a fault and turn-
off the drive’s output
Fault at stop
– the drive will delay
declaring a fault until the run
command is removed
alarm
[1]
flt immediate
[2]
fault at stop
[3]
ALARM
Y
Y
Stopping
Mode
[C119]
(Multi-step Stopping Mode Selection)
When the speed command source is set
to multi-step (SPD COMMAND SRC
(C1)=multi-step), the parameter,
STOPPING MODE (C1), determines the
stopping mode of the HPV 900 Series 2 .
The two selectable methods for the
Stopping Mode parameter are
“Immediate” and “Ramp to stop”.
Note: If the SPD COMMAND SRC (C1)
parameter is set to any other definition
other than “multi-step”, the drive will
behave to the “immediate” stopping mode
(independent of the setting of the
STOPPING MODE (C1) parameter).
The “Immediate” stopping mode requires
the drive to be at zero speed prior to
removing the “Run” command. The
“Immediate“ selection is how the HPV 900
Series 2 has traditionally behaved prior to
the addition of this parameter.
The “Ramp to stop” stopping mode is
intende
d for use when removing the “Run”
command prior to the drive reaching zero
speed (as defined by the AB ZERO SPD
LEV (A1) parameter). When the “Run”
command is removed and the speed
reference is above zero speed, the speed
reference will ramp to zero speed
following the selected s-curve.
immediate
[1]
ramp to stop
[2]
IMMEDIATE
Y
Y
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......