Power Convert A4 Submenu
67
Power Convert A4 Submenu
NOTE: When
Hidden item
appears above a
parameter description, it indicates that its
appearance in the list is controlled by the
HIDDEN ITEMS setting.
See details on page
NOTE: When
Run lock out
appears above a
parameter description, the parameter cannot
be changed when the drive is in the RUN
mode.
Parameter
[Alphanumeric]
Description
Units
Range
Default
Hidden
Item
Run
lockout
ENGLISH
(U3)
METRIC
(U3)
Input L-L Volts
[A401]
(Input Line to Line Voltage)
This parameter sets the input
voltage or AC line input voltage to
the drive.
Vrms
110
– 480
0
N
N
UV Alarm Level
[A402]
(Undervoltage Alarm Level)
The nominal DC bus voltage is
equal to 1.414 times the input line-
to-line voltage (i.e. 1.414*Input L-L
Volts (A4) ). This parameter sets the
level (as a percentage of the
nominal DC bus voltage) at which
an undervoltage alarm will be
declared.
%
40
– 99
90
80
Y
N
UV Fault Level
[A403]
(Undervoltage Fault Level)
The nominal DC bus voltage is
equal to 1.414 times the input line-
to-line voltage (i.e. 1.414*Input L-L
Volts (A4) ). This parameter sets the
level (as a percentage of the
nominal DC bus voltage) at which
an undervoltage fault will be
declared.
%
40
– 99
80
70
Y
N
PWM
Frequency
[A404]
(Carrier Frequency)
This parameter sets the PWM or
‘carrier’ frequency of the drive. The
carrier is defaulted at 10.0 kHz,
which is well out of audible range.
The drive does not derate when the
PWM frequency is set to 10kHz or
below.
For more information on
derating see page 16.
kHz
2.5
– 16.0
10.0
N
N
Extern
Reactance
[A405]
(External Reactance)
This parameter sets the externally
connected reactance (as a
percentage of base impedance)
between the drive and the motor.
Units in percent of reactance.
%
0.0
– 10.0
0.0
Y
N
Id Reg Diff Gain
[A406]
(Current Regulator Differential Gain
for Flux Generation)
The differential gain for the current
regulator flux generation. This
parameter is meant for advanced
operation; therefore, the parameter
will rarely need to be changed from
the default value.
none
0.00
– 1.20
1.00
i,
iii
Y
N
0.00
ii
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......