Interconnections
34
Analog Outputs
The HPV 900 Series 2 has two programmable
differential analog output channels. The two
analog output channels were designed for
diagnostic help.
For more information on
programming the analog output channels, see
Analog Outputs C4 Submenu on page 106.
The analog output channels are bipolar and
have a voltage range of
10VDC.
Available with the analog channels is multiplier
gain parameters (ANA 1 OUT GAIN and ANA
2 OUT GAIN) and a bias or offset parameters
(ANA 1 OUT OFFSET and ANA 2 OUT
OFFSET). These parameters are used to scale
the user’s analog outputs to the proper range
for the drive software. The formula below
shows the scaling effects of these two
parameters.
voltage
output
channel
analog
BIAS
OFFSET
creates
software
drive
signal
The scaling of the analog output signals is
shown below.
The connection of these two inputs is shown in
Figure 26.
Figure 26: Analog Outputs
As a reference, please refer to the table below
if replacing an HPV900 or HPV600 with the
HPV900 Series 2 drive.
Terminal
Description
Analog Output Connections
HPV900
Series 2
HPV900
HPV600
option
card
analog common
TB2-2
TB1-34
AC
analog output 1
TB2-8
TB1-33
A1
analog output 2
TB2-1
TB1-35
A2
Shield
TB2-7
TB1-36
N/A
Table 8: Analog Output Connections
Electrical Installation
Input Power Connections
Terminals: R, S, and T provide connections for
AC input power.
Motor Lead Connections
U, V, & W terminals provide connection points
for the motor leads.
DC Choke Connections
Ter1 and +2 provide connection points
for a user supplied DC choke. A two position
removable link is provided to the pair of
terminals. With this link, the drive can be
operated without the use of a DC choke. All
HPV 900 Series 2 drives contain internal DC
reactors.
Brake Resistor Connections
Terminals B1 and B2 provide connection
points for an external user supplied braking
resistor. Connect the external brake resistor
between terminals B1 and B2. Terminals: +
and - are the positive and negative rails of the
DC bus (see Figure 27, Figure 28, Figure 29,
and Figure 30).
Equipment Grounding
A terminal block is provided for the required
user supplied equipment grounding.
Control Circuit
Observe the following precautions:
Refer to Figure 8 on page 25 for completing
encoder connections; analog inputs; logic
inputs; and logic outputs at the HPV 900
Series 2’s Control Board.
IMPORTANT
Parameter adjustments will have to be made
for the specific analog input, logic inputs, and
logic outputs to be used for the installation.
1
2
8
7
analog output 2
analog output common
analog output 1
shield
TB2
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......