User Switches C1 Submenu
85
Parameter
[Alphanumeric]
Description
Choices
Default
Hidden
item
Run
lockout
ENGLISH
(U3)
METRIC
(U3)
Ser2 Flt
Mode
[C124]
(Serial Mode 2 Fault Mode)
Used only with serial protocol (mode 2)
This parameter defines the reaction to a
serial communications fault while in Serial
Mode 2. There are three possible
settings:
Immediate
– upon sensing a serial
communications fault while in the run
mode will result in an immediate stop.
The equivalent to removal of the
“Drive Enable” logic input.
Run Remove
– upon sensing a serial
communications fault while in the run
mode, the drive will react in the same
manner that removal of the run
command would react. In this case,
the type of stop will be defined by the
STOPPING MODE (C1) parameter.
Rescue
– upon sensing a serial
communications fault while in the run
mode, an attempt will be made to
continue to run at a low speed to the
next floor. Upon sensing the fault, the
drive will decelerate to a creep speed
and continue to run at that speed until
the first of the two following
termination conditions are reached.
The hardware “Drive Enable”
logic input is removed.
A timer set by parameter SER2
RS CPR TIME (A1) has elapsed.
Immediate
[1]
run remove
[2]
rescue
[3]
IMMEDIATE
Y
Y
Drv Fast
Disable
[C125]
(Drive Fast Disable)
Addresses how fast the drive responds to
the removal of the DRIVE ENABLE logic
input.
enable
[1]
disable
[0]
DISABLE
Y
Y
Speed Reg
Type
i,ii
[C126]
(Speed Regulator Type
i
,ii
)
Chooses speed regulator: Ereg or PI
regulator. Magnetek recommends the use
of the Elevator Speed Regulator (Ereg) for
better elevator performance. If set to
external regulator, the drive will be
configured as a torque controller.
IMPORTANT
This assumes the car controller is doing
its own closed-loop speed regulation. (i.e.
a completely closed outer speed loop with
the car controller having its own encoder
feedback).
The source of the external torque
command is determined by the EXT
TORQ CMD SRC (C1) parameter.
For more information, see SPEED REG
TYPE on page 96.
elev spd reg
i
,ii
[1]
pi speed reg
i
,ii
[2]
external reg
i
,ii
[3]
ELEV SPD REG
i,ii
Y
i
,ii
Y
i
,ii
i
Parameter accessible through
CLOSED LOOP (U9)
Operation
ii
Parameter accessibly through
PM (U9)
Operation
iii
Parameter accessible through
OPEN LOOP(U9)
Operation
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......