![Magnetek HPV 900 Series 2 Скачать руководство пользователя страница 100](http://html1.mh-extra.com/html/magnetek/hpv-900-series-2/hpv-900-series-2_technical-manual_3606659100.webp)
Motor A5 Submenu
78
Parameter
[
Alphanumeric]
Description
Units
Range
Default
Hidden
Item
Run
lockout
ENGLISH
(U3)
METRIC
(U3)
OL Align
Scale
ii
[A525]
(Open-Loop Alignment Scale
ii
) The drive
automatically calculates the torque
constant. This value can scale the
calculated torque constant to provide
better performance.
none
ii
0.50
– 2.00
ii
0.78
ii
N
ii
N
ii
Encoder
Ang Ofst
ii
[A526]
(Encoder Angle Offset
ii
) This parameter
contains the value of the alignment
determined during the alignment
procedure. For more information on the
alignment procedure, see Magnetek PM
Start-Up Procedure on page ix.
none
ii
0
– 35999
ii
30000
ii
N
ii
Y
ii
Table 14: Motor A5 Submenu
OVLD START LEVEL
(Motor Overload Start Level)
This parameter defines maximum current at
which motor can run continuously. This
parameter is also one of the two parameters
that define the motor overload curve.
The motor overload parameters can be
adjusted by the user. The following two
parameters are used to define the motor
overload curve.
motor current overload start level (OVLD
START LEVEL(A5)) parameter
motor current time out (OVLD TIME
OUT(A5)) parameter
Three overload curves are shown. Curve #1 is
the default motor overload curve. The
parameter settings that define the three
overload curves are shown.
OVLD
START
LEVEL
OVLD
TIME
OUT
curve #1
110%
60 sec
curve #2
110%
40 sec
curve #3
120%
70 sec
Motor Overload Parameters
When the motor had exceeded the user
defined motor overload curve, the drive will
declare a motor overload alarm.
The motor overload alarm can also be
assigned to a logic output.
Under the POWER DATA display sub-menu,
the MOTOR OVERLOAD (D2) value displays
the percentage of motor overload trip level
reached. Once this value reaches 100% the
motor has exceeded its user defined overload
curve and a motor overload alarm is declared
by the drive.
The drive will only declare a motor overload
and the user is responsible for action.
But, if the user wants the drive to declare a
fault on a motor overload the following need to
be completed:
logic output configured to MTR
OVERLOAD
logic input configured to EXT FAULT
wire the EXT FAULT logic input terminal to
the MTR OVERLOAD logic output terminal
wire the logic input common terminal to the
logic output common
With the above set-up, the drive will then
declare an External Fault on a motor overload
(Motor Ovrld Sel) C1
This parameter selects the action to be taken
by the drive when declareing a Motor
Overload.
Alarm
– the drive only declares a motor
overload and the user is responsible for
action
Flt immediate
– the drive will immediately
declare a fault and turn-
off the drive’s
output
Fault at stop
– the drive will delay declaring
a fault until the run command is removed
8:55
ALARM!
MTR OVERLOAD
READY
RUN
USER
FAULT
TORQUE
LIMIT
SUB MENU
DATA ENTRY
D2 8:55
Motor Overload
+00100 %
READY
RUN
USER
FAULT
TORQUE
LIMIT
SUB MENU
DATA ENTRY
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......