Motor A5 Submenu
77
Parameter
[
Alphanumeric]
Description
Units
Range
Default
Hidden
Item
Run
lockout
ENGLISH
(U3)
METRIC
(U3)
Motor
Mid
Freq
iii
[A514]
(V/Hz Pattern Middle Frequency
iii
) This
parameter sets middle frequency used to
define the V/Hz pattern. Note: a SETUP
FLT #9 will occur if the below formula is
not meet.
FREQ
EXCIT
RATED
FREQ
MID
MOTOR
FREQ
MIN
MOTOR
Hz
iii
0.1
– 40.0
iii
3.0
iii
N
iii
Y
iii
Ovld Start
Level
[A518]
(Motor Overload Start Level)
This parameter defines maximum current
at which motor can run continuously. This
parameter is also one of the two
parameters that define the motor overload
curve. Units in percent of rated current.
For more information, see OVLD START
LEVEL on page 78.
%
100
– 150
110
Y
Y
Ovld Time
Out
[A519]
(Motor Overload Time Out)
This parameter defines the amount of
time before a motor overload alarm
occurs when the motor is running at the
current level defined below:
current
motor
rated
40%
:
LEVEL
START
OVLD
This is the other parameter used to define
the overload curve. For more information,
see OVLD START LEVEL on page 78.
sec
5.0
– 120.0
60.0
Y
Y
Stator
Resist
[A520]
(Stator Resistance) This parameter sets
the amount of resistance in the motor
stator, as a percent of the BASE
IMPEDANCE, which appears in the
Power Data D2 Submenu.
%
0.0
– 20.0
1.5
i,
iii
Y
N
7.0
ii
Motor Iron
Loss
[A521]
(Motor Iron Losses) This parameter sets
the motor iron loss at rated frequency.
Units in percent of rated power.
%
0.0
– 15.0
0.5
Y
N
Motor Mech
Loss
[A522]
(Motor Mechanical Losses)
This parameter sets the motor mechanical
losses at rated frequency. Units in
percent of rated power.
%
0.0
– 15.0
1.0
Y
N
D Axis
Inductance
ii
[A523]
(Magnet/Flux Axis Equivalent Circuit
Inductance
ii
) This parameter sets amount
of inductance in flux producing equivalent
circuit of the vector controlled PM motor.
Higher inductances are used for higher
horsepower motors., but it is best if
obtained from motor specifications.
mH
ii
0.50
– 150.00
ii
10.00
ii
30.00
ii
N
ii
N
ii
Q Axis
Inductance
ii
[A524]
(Torque Axis Equivalent Circuit
Inductance
ii
) This parameter sets
amount of inductance in torque producing
equivalent circuit of the vector controlled
PM motor. Higher inductances are used
for higher horsepower motors., but it is
best if obtained from motor specifications.
mH
ii
0.50
– 150.00
ii
10.00
ii
30.00
ii
N
ii
N
ii
i
Parameter accessible through
CLOSED LOOP (U9)
Operation
ii
Parameter accessibly through
PM (U9)
Operation
iii
Parameter accessible through
OPEN LOOP(U9)
Operation
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......