User Switches C1 Submenu
87
Parameter
[Alphanumeric]
Description
Choices
Default
Hidden
item
Run
lockout
ENGLISH
(U3)
METRIC
(U3)
Fault Reset
Src
[C131]
(Fault Reset Source)
This parameter determines the source of
the drive’s external fault reset from one of
the following sources: an external fault
reset signal from a logic input (external
tb), a fault reset signal transferred across
a serial channel (serial), or the drive
automatically resets the faults (automatic).
The user also has the option to reset
faults directly through the operator.
Automatic Fault Reset
If the fault reset source is set to automatic,
the faults will be reset according to the
setting of the FLT RESET DELAY (A1)
and FLT RESETS/HOUR (A1)
parameters. When a logic input is defined
as “fault reset” and this logic input signal
is transitioned from false to true: an active
fault will be reset and automatic fault reset
counter (defined by FLT
RESETS/HOUR(A1)) will be reset to zero.
CAUTION
If the run signal is asserted at the time of
a fault reset, the drive will immediately go
into a run state. Unless using the auto-
fault reset function (FAULT RESET SRC
(C1)=automatic), then the run command
needs to be cycled to be reset
automatically, but will reset if initiated by a
logic input without cycling the run
command.
external tb
[1]
serial
[2]
automatic
[3]
EXTERNAL TB
Y
Y
Overspd Test
Src
[C132]
(Overspeed Test Source)
This switch determines the source of the
overspeed test. Operation of the
overspeed test function is specified by the
OVRSPEED MULT (A1) parameter.
Regardless of the setting of this
parameter, the user can call for the
overspeed test via the Digital Operator.
external tb
[1]
serial
[2]
EXTERNAL TB
Y
Y
PreTorque
Src
[C133]
(Pre-Torque Source)
This parameter sets the source of the
pre-torque command.
none
[0]
analog input
[1]
serial
[2]
None
Y
Y
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......