Drive A1 Submenu
44
Parameter
[
Alphanumeric]
Description
Units
Range
Default
Hidden
Item
Run
lockout
ENGLISH
(U3)
METRIC
(U3)
DC Stop
Freq
iii
[A127]
(DC Injection Stopping Frequency
ii
) The
frequency at which DC injection begins to
occur when the drive is decelerating to a
stop. If ramp to stop is selected and the run
command is removed, the drive decelerates
from its current speed to the DC stop
frequency and then DC injection is applied.
Hz
iii
0.0
– 10.0
iii
0.5
iii
N
iii
Y
iii
DC Start
Time
iii
[A128]
(DC Injection Current Start Time
iii
) The time
DC injection current is applied following a
valid run command until the release of the
speed command. After receiving a valid run
command the drive will maintain DC Start
Level current for Dc Start Time in seconds
before releasing the internal speed
reference allowing the drive to ramp up in
speed. At the start, it is important to have
DC injection current before and after the
mechanical brake is picked to allow the
brake to fully open.
sec
iii
0.00
– 5.00
iii
1.00
iii
N
iii
Y
iii
DC Stop
Time
iii
[A129]
(DC Injection Current Stop Time
iii
) The time
the level of DC injection current at stop is at
DC STOP LEVEL. If ramp to stop is
selected, the drive will ramp down in speed
following removal of the run command to the
DC Stop Freq and will then output DC Stop
Level current for DC Stop Time seconds. At
the stop, it is important to have DC injection
current after the mechanical brake is closed
to allow the brake to fully close.
sec
iii
0.00
– 5.00
iii
1.00
iii
N
iii
Y
iii
Overspeed
Level
i,ii
[A130]
(Overspeed Level
i,
ii
) This parameter sets
the percentage of rated speed the drive uses
(in conjunction with OVERSPEED TIME,
below) to determine when an OVERSPEED
FLT occurs. Units in percent of contract
speed.
%
i
,
ii
100.0
–
150.0
i
,
ii
115.0
i
,
ii
Y
i,
ii
N
i,
ii
Overspeed
Time
i,ii
[A131]
(Overspeed Time
i,
ii
) This parameter sets the
time that the drive can be at or above the
OVERSPEED LEVEL (A1), before the drive
declares an OVERSPEED FLT.
sec
i
,
ii
0.00
– 3.00
i
,
ii
1.00
i
,
ii
Y
i,
ii
N
i,
ii
Overspeed
Mult
[A132]
(Over Speed Multiplier) This parameter sets
the percentage of contract speed for the
OVERSPEED TEST (U4).
%
100.0
– 150.0
125.0
Y
N
Stalltest
Level
iii
[A133]
(Stall Test Level
iii
) This parameter sets the
percentage of motor current the drive uses
(in conjunction with STALL FAULT
TIME(A1)) to determine when an STALL
FAULT occurs. In order for a STALL TEST
FAULT to occur, it must be enabled by the
STALL TEST ENA (C1) parameter. Units in
percent of rated motor current.
%
iii
0.0
– 200.0
iii
200.0
iii
N
iii
Y
iii
i
Parameter accessible through
CLOSED LOOP (U9)
Operation
ii
Parameter accessibly through
PM (U9)
Operation
iii
Parameter accessible through
OPEN LOOP(U9)
Operation
Содержание HPV 900 Series 2
Страница 4: ......
Страница 195: ...APPENDIX Dimensions Mounting Holes Weights 173 Figure 46 Frame 2 Dimensions Mounting Holes and Weight...
Страница 196: ...APPENDIX Dimensions Mounting Holes Weights 174 Figure 47 Frame 3 Dimensions Mounting Holes and Weight...
Страница 197: ...APPENDIX Dimensions Mounting Holes Weights 175 Figure 48 Frame 3 5 Dimensions Mounting Holes and Weight...
Страница 198: ...APPENDIX Dimensions Mounting Holes Weights 176 Figure 49 Frame 4 Dimensions Mounting Holes and Weight...
Страница 199: ...APPENDIX Dimensions Mounting Holes Weights 177 Figure 50 Frame 5 Dimensions Mounting Holes and Weight...
Страница 227: ...205 Z Z MARKER LOST 150 Zero Speed Level parameter 47 Zero Speed logic output 105 Zero Speed Time parameter 47...
Страница 228: ......
Страница 229: ......