4. Trial Operation
4-8
LCD Display
Description
Tuning Time
Accel/Decel is performed
repeatedly to find motor
constant (Tr) so that DB
Resistor should be connected
before starting tuning.
Otherwise, “Over Voltage ” trip
will occur.
20 ~ 60(Sec)
When auto-tuning is complete
successfully, “None” is
displayed. If error occurs during
auto-
tuning, “[][] Error” is
displayed. In this case,
verify
motor parameters and
encoder setting is done
properly
and redo the auto-
tuning. If the problem persists,
contact LS representative.
Total
3 ~ 5 (Min.) is
required
FWD/REV LED on keypad will blink during Auto-tuning.
If setting PAR_24 (Auto tuning) to “ ALL2 ”, all procedure is same as “ALL1”
except Encoder Testing will be skipped.
Motor constants of each can be selected and separately tuned.
(Encoder Test, Rs Tuning, Lsigma, Flux Curr, Ls Tuning, Tr Tuning)
If encoder phase (A, B) or inverter output wiring is switched during Auto-tuning,
“ Enc AB Chgd ” message will be displayed. In this case, changing PAR_11
(Enc Dir Set) setting from “A Phase Lead” to “B Phase Lead” (or oppositely)
will erase the need for changing the wiring.
PA R
▶
Auto tuning
2 5 T r Tu n i n g
PA R
▶
Auto tuning
2 5 N o n e
PA R
▶
Auto tuning
2 5 [ ] [ ] E r r o r