6. Function Description
6-80
Code
Display
Definition
Unit
Function description
Name
Setting
range
0 → 10V
0 ~ (AIO_03 Ai1 In X1)/2
10 → 0V
0 ~ (AIO_03 Ai1 In X1)/2
0 → 20mA
0 ~ (AIO_03 Ai1 In X1)/2
20 → 0mA
0 ~ (AIO_03 Ai1 In X1)/2
Below x1
If the analog input according to AIO_02 Ai1
Source is under the range of below, it means
analog loss
-
10 → 10V
(AIO_07 Ai1 -In X1)
~ (AIO_03 Ai1 In X1)
10 →
-10V
(AIO_07 Ai1 -In X1)
~ (AIO_03 Ai1 In X1)
0 →
10V
0 ~ (AIO_03 Ai1 In X1)
10 → 0V
0 ~ (AIO_03 Ai1 In X1)
0 → 20mA
0 ~ (AIO_03 Ai1 In X1)
20 → 0mA
0 ~ (AIO_03 Ai1 In X1)
There are same functions for choosing the criterion of command loss of the other multi-function analog input.
4) Time out for command loss of Multi-function analog input (AIO_73 Time out)
It means the time for judging the loss time of analog input. If the time that is set at AIO_73 Time Out is passed, it can
be considered as analog input loss
Code
Display
Definition
Unit
Function description
Name
Setting
range
AIO_73
Time out
Time for loss of
Multi-function analog
input
0.1 ~ 120.0
sec
It sets the time for judging command loss when
the analog input is keeping from the moment of
satisfying the condition set at multi-function
analog input loss criterion until the set time.
AIO_73 Time out can be applied
세
AIO_12 Ai1 Wbroken, AIO_24 Ai2 Wbroken, AIO_36 Ai3 Wbroken.
(In the case of I/O(EXTN_I/O, it can also be applied to AIO_48 Ai4 Wbroken, AIO_60 Ai5 Wbroken.)
If multi-functional analog input is lost, the inverter stops by decelerated stop or by Free Run. The stopping method
can be set up at DIO_97. See DIO_97 for further details.