11. Option Devices
11-3
11.1.3 Encoder division output
Only available when Encoder Division Output Option Card is installed.
Sets the division ratio for monitoring the Encoder pulse signals.
Code
Address
LCD
display
Description
Setting range
Unit
Factory
setting
PAR_32
7320
EncDiv Ratio Encoder Pulse Output Division Rate
1 ~ 1128
1
PAR_33
7321
EncDivFilter
Encoder Division Output Filter
0 ~ 15
0
Encoder division output option card outputs one pulse signal when input pulse number matches the value set in PAR_32.
A/B pulse output follows input pulse phase. The relationship between output of A, B pulse follows the same as input
pulse.
Division ration can be set within the range of 1 (1 output pulse per 1 input pulse) ~ 1/128(1 output pulse to 128
input pulse).
PAR_32 setting range: 0001 ~ 1128. Division ratio cannot be set higher than 1 and only 1 or 2 can be set for
numerator. The below is Division ratio calculation formula.
N refers to the value from thousand (
0
000) and M refers to value less than thousand (0
000
)
PAR_32 set value = N
1000 + M.
Division ratio = (1+N)/M
Setting range: N (0, 1), M (1 ~ 128)
PAR_32 = [] [] [] []
When PAR_32 setting value is below 1000 (N=0), a numerator value becomes 1 and when above 1000
(N=1), a numerator value becomes 2. For example, if PAR_32 is set to 15, the division ratio is 1/15 and if
1015, the ratio is 2/15. Division ratio is settable up to 1/128 and greater than 1 is not settable. Using Up key
on the keypad PAR_32 value is increased and increase routine is 1
2
3
4
…
127
128(Division ratio: 1/128)
1002 (Division ratio: 1)
1003
…
1128 (Division ratio: 1/64) and
decrease routine (using Down key on the keypad) is the same as increase routine.
N M