Chapter 8 Communication Function
8-18
Address
Parameter
Scale unit R/W
Allotment for Bits
B0 H/W Diag
0334h
N/A
-
-
0335h~
033Fh
N/A
-
-
-
0340h
On Time date
0
Day
R
Total number date of inverter power On
0341h
On Time minute
0
Min
R
Total minute except for total date of inverter On Time
0342h
Run Time date
0
Day
R
Total number day of inverter run
0343h
Run Time minute
0
Min
R
Total minute except for total day of Run Time
0344h
Fan Time date
0
Day
R
Total day of cooling fan run
0345h
Fan Time minute
0
Min
R
Total minute except for total day of Fan time
0346h
N/A
-
-
-
0347h
N/A
-
-
-
0348h
N/A
-
-
-
0349h
N/A
-
-
-
034Ah
Option 1
-
-
0: None
1: RS485
2: DeviceNet
3: Profibus,
4: FNet
5: LONWORKS
6: N/A
7: N/A
8: BACNet
9: N/A
10: N/A
11: Synchro option
034Bh
N/A
034Ch
N/A
0380h
Frequency command
0.01
Hz
R/W
Frequency command setting
E.g.) It operates 10Hz (300rpm based on 4 polaritys) when 03E8h (=1000) is
transferred.
0381h
RPM command
1
rpm
R/W
Command rpm setting (FUN_02 is Option/Int485)
E.g.) It operates 1000rpm when 03E8 (=1000) is transferred.
0382h
Run command
B7
N/A
B6
N/A
B5
N/A
B4
N/A
B3
BX (0
1: Free-run stop)
B2
RST (0
1: Trip reset)
B1
0: Reverse command 1: Forward command
B0
0: Stop commands
1: Run command
E.g.) Forward command: 0003h, Reverse command: 0001h
BX and RST are only available to write. It will be read to 0.
It can operate when FUN_01 is Option/Int485.
0383h
Acceleration time
0.1
sec
R/W Acceleration time setting
0384h
Deceleration time
0.1
sec
R/W Deceleration time setting