6. Function Description
6-18
No
Set value
No
Set value
No
Set value
3
Spd Det.
11
INV OH Warn
19
Brake Output
4
Spd Det (ABS)
12
Speed Agree
5
Spd Arrival
13
Trq Det.
6
Timer Out
14
Trq Lmt Det.
7
LV Warn
15
OverLoad
2.1) Not used
It is set unless multi-function output is not used as any function listed above.
2.2) INV ready
INV Ready becomes ON when inverter is ready to operate normally. If trip signal occurs, INV Ready is left OPEN
immediately as shown in the figure below.
2.3) Zero Spd Det
Detects zero speed of motor. See the figure below.
Code
Display
Description
Range
Unit
Default
DIO_47
ZSD Level
Zero Speed Detect Level
0.0 ~ 480.0
rpm
10
DIO_48
ZSD Band
ZSD hysteresis band
0.1 ~ 10.0
%
0.5
DIO_48(ZSD Band) is set as the percentage of FUN_04 Max motor speed.
2.4) Spd Det.
–
Polarity valid / Spd Det.(ABS)
–
Polarity invalid
This is ON when the real motor speed reaches the arbitrary speed. The polarity of detecting speed is valid for Spd Det.
Trip signal
AX1
OPEN
CLOSE
CLOSE
ON
OFF
OFF
TIME
SPEED
DIO_47
OPEN
DIO_48
CLOSE
CLOSE
Detection
signal