6. Function Description
6-78
2) Adjusting Bias: Out Y1 and Gain: Out Y2 by Loader
AIO_04 Ai1 Out Y1 adjustment
Connect the voltage source or current source between Ai1 ~ 5G, multi-analog terminals of standard I/O devices.
Feed 0[V] or 0[mA] with the AIO_03 In X1 set as 0% and then follow as below.
Key
LCD Display
Description
Initial Gain (Factory setting)
PROG
When pressing the [PROG] key, current output [%] to input
value is displayed on the first line and current setting bias
on the second line.
▲
If you want to adjust Bias to be 0.00% at 0V input on the
first line, adjust it to be 0.00% using [
▲
(Up)] key.
ENT
After setting 0.00% Bias and pressing [ENT] key, it is
displayed and the changed value is saved.
AIO_06 Ai1 Out Y2 adjustment
Connect the voltage source or current source between Ai1 ~ 5G, multi-analog terminals of standard I/O devices.
Feed 10[V] or 20[mA] with AIO_05 In X2 set as 100% and then follow as below.
Key
LCD Display
Description
Initial Gain (Factory setting)
PROG
When pressing the [PROG] key, current output [%] to input
value is displayed on the first line and current setting gain
on the second line.
▲
If you want to adjust Gain to be 100.00% at 10V input on
the first line, adjust gain to be 102.00% using [
▲
(Up)]
key.
ENT
After setting 102.00% Gain and pressing [ENT] key, it is
displayed and the changed gain is saved.
AIO
▶
Ai1 Out Y1
04 0.00 %
AIO
▶
Ai1 0.18 %
04 Bias
0.00 %
AIO
▶
Ai1 0.00 %
04 Bias
0.18 %
AIO
▶
Ai1 Out Y1
04 0.18 %
AIO
▶
Ai1 Out Y2
06 100.00 %
AIO
▶
Ai1
98.00 %
06 Gain 100.00 %
AIO
▶
Ai1 100.00 %
06 Gain
102.00 %
AIO
▶
Ai1 Out Y2
06 102.00 %