6. Function Description
6-55
To return to normal mode, release the signal from ‘Battery Run’ mode of multi
-function input turned On.
Additional wiring for battery-operated mode is as shown below.
-. Connect the 2 terminals among main circuit input terminal R, S, T to battery positive through MC (Magnetic
Contactor).
-. Connect N (-) terminal of main circuit to battery negative.
-. Input UPS auxiliary power supply 220V to AC1 and AC2
.
PE
R
S
T
G
U
V
W
IM
GE
A+
E
Encdoer
(Line Drive Type)
MC
G
Encoder A
Phase Input
Shield
Battery Run Signal Input
STARVERT - iV5
Multi-function (P1~P7)
Encoder B
Phase Input
Power Supply (5V)
Common (0V)
B+
A-
B-
AC1
AC2
UPS
220V
Insulated Transformer
Battery
Min. 24V
MC
3P AC
Input
N(-)
(+)
(-)
Note)
: Main circuit
, : Control circuit
Features of battery-operated function
-.In battery-
operated mode, LED on the right side of the loader for current operation mode and ‘BAT’ are
displayed by turns.
-.In case multi-function output sets
to ‘INV Ready’, it turns off during battery
-operated mode.
-. After battery power is energized to inverter, inverter will start 2 seconds later after the time for releasing the
low voltage trip and raising the internal voltage.
-.If voltage is falling less than about 53% of FUN_77 set value, it sets down as low voltage trip so it is detected a
trip.
-.To return to main power, main power must be energized after releasing the magnetic contactor and signal from
the battery and then low voltage trip is detected.
-.Operation speed (FUN_77) must be determined according to battery voltage (FUN_76), base speed (PAR_17)
and motor rated voltage (PAR_18). Please operate the inverter with low speed by battery capacity.