Chapter 8 Communication Function
8-4
Judgment standard and Protection in case of a problem with the communication for a certain period of time
If communication is lost for a time set inEXT_37 when command is set at EXT_36, inverter will be operated as below.
Setting Item
Function
None
Speed command is directly the operating frequency without protective movements.
Free-Run
The inverter blocks output. The motor continues free run.
Stop
Decelerating stop
FUN_01 Run/Stop Src is Int485 prior to run this function. If communication is disconnected for EXT_37, keypad
display is as below. ‘rpm’ value in lower line is current operation speed.
8.5 Special communication area setting
Entire iV5 communication memory map
Communication Area
Memory Map
Description
Common iS5 compatible
communication area
0h0000 ~ 0h00FF
Area compatible with iS5
Common iS7
communication area
0h0300 ~ 0h037F
Inverter monitoring area
0h0380 ~ 0h03DF
Inverter control area
0h03E0 ~ 0h03FF
Inverter memory control area
Common communication
area
0h0500 ~ 0h05FF
Common communication area
0.0rpm SPD
00 LOI 500 rpm