5. Function Code Table
5-11
CODE
NO.
Comm.
Addr
CODE NAME
LCD DISPLAY
SETTING DATA
Adjustment
During Run
RANGE
UNIT
DEFAULT
FUN_58 743A
Switching frequency
select
PWM Freq
2.5 ~ 10.0
4)
kHz
According
to inverter
capacity
No
FUN_59 743B Power on Run selection Power-on Run
0 (No) / 1 (Yes)
-
0 (No)
Yes
FUN_60 743C Restart after fault reset RST Restart
0 (No) / 1 (Yes)
-
0 (No)
Yes
FUN_61 743D
Number of auto restart
try
Retry Number
0 ~ 10
-
0
Yes
FUN_62 743E
Delay time before Auto
restart
Retry Delay
0.0 ~ 60.0
sec
1.0
Yes
FUN_63 743F
Wait time for Restart
upon Stop
Restart Time
5)
0.00 ~ 10.00
sec
0.00
No
FUN_64 7440
Overspeed Detection
Time
OverSpdLevel
100.0 ~ 130.0
%
120.0
No
FUN_65 7441
Electronic thermal level
for 1 minute
OverSpd Time
0.00 ~ 2.00
sec
0.00
No
FUN_66 7442
Br
ak
e
Open Time
6)
BKOpen Time
0.00 ~ 30.00
sec
0.00
No
FUN_67 7443
Open Speed
6)
BKOpen Spd
0.0 ~ 500.0
rpm
0.0
No
FUN_68 7444
Open Current
6)
Release Curr
0.0 ~ 150.0
%
20.0
No
FUN_69 7445
Close Time
6)
BKClose Time
0.00 ~ 30.00
sec
0.00
No
FUN_70 7446
Close Speed
6)
BKClose Spd
0.0 ~ 500.0
rpm
0.0
No
FUN_71 7447
R
e
g
er
n
er
at
io
n
pr
ev
e
nt
io
n
Run selection
RegenAvd Sel
0 (No) / 1 (Yes)
-
0 (No)
No
FUN_72 7448
Run voltage level
7)
RegenAvd Lvl
600(300) ~
800(400)
V
700(350)
No
FUN_73 7449
Speed limitation
7)
CompFreq Lmt
0.0 ~ 500.0
rpm
100.0
No
FUN_74 744A
Speed P gain
7)
RegenAvd P
0.0 ~ 300.0
%
50.0
Yes
FUN_75 744B
Speed I gain
7)
RegenAvd I
20 ~ 30000
ms
500
Yes
FUN_76 744C
Speed in
battery-operated mode
8)
Batt. Speed
2.5 ~ 200.0
rpm
50.0
No
FUN_77 744D Battery input voltage
8)
Batt. Volt
12 ~ PAR_18
V
48
No
FUN_78 744E
Check of input
phase-open
PhInOpenChk
0 (No) / 1 (Yes)
-
1 (Yes)
No
FUN_79 7450
Check level of input
phase-open
PhInOpenLvl
2.0 ~ 100.0
V
3.0
Yes
FUN_80 7451
Check of output
phase-open
PhOutOpenChk 0 (No) / 1 (Yes)
-
1 (Yes)
No
FUN_81 7452
Max. auxiliary speed
AuxSpeedMax
0.0~500.0
rpm
10.0
Yes
Содержание LSLV-iV5 Series
Страница 59: ...4 Trial Operation 4 17 ...