6. Function Description
6-48
Load Current (%)
Trip Time
1 minute
FUN_55
FUN_56
[ETH 1min]
[ETH cont]
[Motor i2t Characteristic Curve]
The motor protection is possible by calculating and accumulating I
2
t even in load variation and
frequent run/stop.
6.4.8 Inverter switching frequency select
1) FUN_58 (Inverter switching frequency select)
This parameter affects the audible sound of the motor, noise emission from the inverter, inverter
termperature, and leakage current. If the ambient temperature where the inverter is installed is high or
other equipment may be affected by potential inverter noise, set this value lower. (setting range:
2.5 ~ 10.0
kHz).
Code
LCD display
Description
Setting range
Unit
Factory
setting
FUN_58
PWM Freq
Switching frequency select
kHz
2) Setting range and factory setting of switching frequency
Voltage
Inverter capacity
(kW)
Setting range (kHz)
Factory setting (kHz)
200V
2.2 ~ 22(kW)
2.5 ~ 10(kHz)
8(kHz)
30/37(kW)
2.5 ~ 7(kHz)
5(kHz)
400V
2.2 ~ 22(kW)
2.5 ~ 10(kHz)
8(kHz)
30 ~ 75(kW)
2.5 ~ 7(kHz)
5(kHz)
90 ~ 132(kW)
2.5 ~ 5(kHz)
4(kHz)
160/220(kW)
2.5 ~ 4(kHz)
4(kHz)
280 ~ 375 (kW)
2(kHz)
2(kHz)