ADDITIONAL UL MARKING
1. Short Circuit Rating
“Suitable For Use On A Circuit Capable Of Delivering Not More Than Table1*
RMS Symmetrical Amperes, 240 for rated 240V drives or 480 for rated 480V
drives V
olts Maximum,” or equivalent.
Table1*
Inverter Capacity
Rating
200/400V Class: 5.5kW, 7.5kW, 11kW, 15kW, 18.5 kW, 22kW, 30kW, 37kW
5,000A
400V Class: 45kW, 55kW, 75kW, 90kW, 110kW, 132kW
10,000A
400V Class: 160kW, 220kW
18,000A
2. SHORT CIRCUIT FUSE/BREAKER MARKING
Use Class H or K5 UL Listed Input Fuse and UL Listed Breaker Only. See the table
below for the Voltage and Current rating of the fuses and the breakers.
Input
[V]
Inverter
[kW]
External Fuse
Breaker
Internal Fuse
Current
[A]
Voltage
[V]
Current
[A]
Voltage
[V]
Current
[A]
Voltage
[Vac/dc]
Manufacturer
Model
Number
200
Class
5.5
40
500
50
220
60
250
Hinode Elec
250GH-60
7.5
50
500
60
220
60
250
250GH-60
11
70
500
100
220
125
250
250GH-125
15
100
500
100
220
150
250
250GH-150
18.5
100
500
225
220
175
250
250GH-175
22
125
500
225
220
225
250
250GH-225
30
150
500
225
220
250
250
250GH-250S
37
200
500
225
220
250
250
250GH-250S
400
Class
5.5
20
500
30
460
35
660
660GH-35
7.5
30
500
30
460
35
660
660GH-35
11
35
500
50
460
63
660
660GH-63
15
45
500
60
460
80
660
660GH-80
18.5
60
500
100
460
100
660
660GH-100
22
70
500
100
460
125
660
660GH-125
30
100
500
100
460
125
600
600FH-125S
37
100
500
225
460
150
600
600FH-150S
45
100
500
225
460
200
600
600FH-200S
55
150
500
225
460
200
600
600FH-200S
75
200
500
225
460
125
600
600FH-125S
90
250
500
400
460
200
600
600FH-200S
110
300
500
400
460
200
600
600FH-200S
132
400
500
400
460
300
600
600FH-300S
160
400
500
400
460
300
600
600FH-300S
220
―
―
600
460
600
600
600SPF-600UL
3. FIELD WIRING TERMINAL
1) Use Copper wires only with Copper conductors, 75
℃
2) Input and motor output terminal blocks are intended only for use with ring
type connectors.
4. CAUTION-Risk of Electric Shock
“Before opening the cover, disconnect all power and wait at least 10 minutes”
Units suitable only for use in a pollution degree 2 environment. Be sure to mount
the inverter in a forced-ventilated operating panel.