6. Function Description
6-83
100%
-100%
10V
-10V
AO Bias
100%
-100%
10V
-10V
Initail Value (Bias : 0%, Gain : 100%)
Bias 30% setting
AO Bias
100%
-100%
10V
-10V
50%
-50%
AO Bias
100%
-100%
10V
-10V
50%
-50%
Gain 200% setting Absolute value setting
Multi-function analog output setting types and range are as below
Setting
Description
Output signal level
AiX Value
Analog input value
+10 V: 10V, 20mA
PreRamp Ref
Pre Ramp Reference
+10 V: Max Speed
PostRamp Ref
Post ramp reference
+10 V: Max Speed
ASR Inp Ref
ASR Input Reference
+10 V: Max Speed
Motor Speed
Motor Rotating Speed
+10 V: Max Speed
Motor Spd Est
Estimated motor speed
+10 V: Max Speed
Speed Dev
Speed Deviation
+10 V: Rated slip * 2
ASR Out
ASR Output
+10 V: 250%
Torque Bias
Torque bias
+6 V: 150%
PosTrq Limit
Positive Trq Limit
10V: 250%
NegTrq Limit
Negative Trq Limit
10V: 250%
RegTrq Limit
Regeneration Trq Limit
10V: 250%
Torque Ref
Torque Reference
+10 V: 250%
IqeRef
Torque current ref.
+10V: 250% of rated torque current
Iqe
Torque current
+10V: 250% of rated torque current
Flux Ref
Flux reference
10V: Flux rating * 2
IdeRef
Flux Current ref.
+10V: Rated flux current * 2
Ide
Flux Current
+10V: Rated flux current * 2