6. Function Description
6-79
Speed set
100%
10V
Voltage input
Speed set
20%
30%
10V
Voltage input
In X1 Change
Initial Value
100%
Out Y1(Bias) Change
Speed set
10V
20%
Voltage input
100%
100%
30%
Speed set
20%
70%
Voltage input
10V
In X2 Change
Out Y2(Gain) Change
Speed set
100%
80%
30%
20%
70%
10V
Voltage input
The same procedure is applied to AIO_08 Ai1
–
Out Y1 and AIO_10 Ai1
–
Out Y2 and also to the other multi-function
analog input
For example about multi-function analog input setting , In X1 : 20%, In X2 : 70%, Out Y1 : 30%, Out Y2 :
80% for the 0 ~ 10V input, analog command changes are as follows.
3) Criterion for command loss of Multi analog input Ai1 (AIO_1)
You can choose criterion for command loss of signal that is fed into multi-function analog input.
Code
Display
Definition
Unit
Function description
Name
Setting
range
AIO_12 Ai1 Wbroken
Criterion for
command loss of
Multi analog input Ai1
None
Do not set analog loss
Half of x1
If the analog input according to AIO_02 i1 Source
is under the range of below, it means analog
loss.
-10
→ 10V
(AIO_07 Ai1 -In X1)/2
~ (AIO_03 Ai1 In X1)/2
10 →
-10V
(AIO_07 Ai1 -In X1)/2
~ (AIO_03 Ai1
In X1)/2