5. Function Code Table
5-5
CODE
NO.
Comm.
Addr
CODE NAME
LCD
DISPLAY
SETTING DATA
Adjustment
During Run
RANGE
UNIT DEFAULT
11 (Inv OH Warn)
12 (Spd Agree)
13 (Trq Det.)
14 (Trq Lmt Det.)
15 (OverLoad)
16 (Stop)
17 (MC on/off)
18 (Steady)
19 (Brake Output)
25 (WEB Break)
1)
26 (Up To Spd)
1)
27 (False Core)
1
)
DIO_42 722A
Definition of AX2 AX2 Define
Same as the range of
‘DIO_41’
-
0
(Not Used)
Yes
DIO_43 722B
Definition of OC1 OC1 Define
-
0
(Not Used)
Yes
DIO_46 722E
Fault relay mode
selection
Relay Mode
000 ~ 111
bit
011
Yes
DIO_47 722F
Zero speed
detection level
ZSD Level
0.0 ~ 480.0
rpm
10.0
Yes
DIO_48 7230
Zero speed
detection band
ZSD Band
0.1 ~ 10.0
%
0.5
Yes
DIO_49 7231
Speed detection
level
SD Level
-3600 ~ 3600
rpm
0
Yes
DIO_50 7232
Speed detection
band
SD Band
0.1 ~ 10.0
%
0.5
Yes
DIO_51 7233
Speed arrival band
SA Band
0.5
Yes
DIO_52 7234
Speed deviation
band
SEQ Band
0.5
Yes
DIO_53 7235
Torque detection
level
TD Level
0.0 ~ 250.0
%
0.0
Yes
DIO_54 7236
Torque detection
band
TD Band
0.1 ~ 10.0
%
0.5
Yes
DIO_55 7237
Timer On delay time TimerOn Dly
0.1 ~ 3600.0
sec
0.1
Yes
DIO_56 7238
Timer Off delay time TimerOff Dly
0.1 ~ 3600.0
sec
0.1
Yes
DIO_57
7239
Ov
er
lo
a
d
Warning level
OL Level
30 ~ 250
%
150
Yes
DIO_58 723A
Warning time
OL Time
0 ~ 30
sec
10
Yes
DIO_59 723B
Trip selection
OLT Select
0 (No)
1 (Yes)
-
1 (Yes)
Yes
DIO_60 723C
Trip level
OLT Level
30 ~ 250
%
180
Yes
DIO_61 723D
Trip time
OLT Time
0 ~ 60
sec
60
Yes