5. Function Code Table
5-15
CODE
NO.
Comm.
Addr.
CODE NAME
LCD DISPLAY
SETTING DATA
Adjustment
During Run
RANGE
UNIT DEFAULT
5 (Ax Kpd Ax)
6 (Ax Ax Kpd)
7 (Ax Ax Ax)
8 (Opt Opt Opt)
CON_34 7522
Limit in forward
run
Pos Trq Lmt
0.0 ~ 250.0
%
150.0
Yes
CON_35 7523
Limit in reverse
run
Neg Trq Lmt
150.0
Yes
CON_36 7524
Limit in
regeneration
Reg Trq Lmt
150.0
Yes
CON_37 7525
Bias source
selection
Trq Bias Src
0 (None)
1 (Analog)
2 (Keypad)
3 (Option)
-
0 (None)
No
CON_38 7526
Bias quantity
Trq Bias
-150.0 ~ 150.0
%
0.0
Yes
CON_39 7527
Bias
feedforward
Trq Bias FF
0.0
Yes
CON_40 7528
Balance
quantity
Trq Balance
0.0 ~ 100.0
%
50.0
Yes
CON_54 7536
S
pe
e
d
S
e
arc
h
Speed Search
selection
Speed Search
0000~ 1111
(Bit setting)
-
0100
No
CON_75 754B
Speed Search
time
4)
SS Time
10 ~ 60000
ms
300
No
CON_76 754C
Speed Search
P gain
4)
SS P Gain
1.0 ~ 300.0
%
100.0
Yes
CON_77 754D
Speed Search I
gain
4)
SS I Gain
1.0 ~ 300.0
%
100.0
Yes
CON_78 754E
Speed Search
LPF
4)
SS LPF
0.1 ~ 300.0
ms
33.3
Yes
CON_79 754F
Speed limit of
Speed/Torque
switch-over
Spd Lmt Src
0.1 ~
Max Speed
rpm
1800.0
No
CON_80 7550
Speed bias of
speed/torque
SpdLmtBias
100.0 ~
Max Speed
rpm
100.0
No
Note)
1) It will be displayed only when the E/L_IO board is installed.
2) It will be displayed only when the SYNC_IO board is installed.
3) It will be displayed when CON_21 (Process PID type) is set to SpeedSet.
4) It will be displayed when CON_01 is set to Sensorless.